{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05302","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05302","canonicalUrl":"https://aoctrl.com/schneider/A9F05302","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05302","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05302, miniature circuit breaker, 3P, 2 A, D curve, 50 kA Icu at 415 V AC, DIN rail.","salesMarkdown":"The Schneider Electric A9F05302 is an Acti9 iC60N miniature circuit breaker, 3-pole, rated 2 A with a D tripping curve. It carries a 50 kA Icu breaking capacity at 415 V AC per EN/IEC 60947-2 and 6 kA Icn at 400 V per EN/IEC 60898-1 — the dual standard rating means it qualifies for both industrial (60947-2) and domestic/commercial (60898-1) installations, so you can spec it into a distribution board or an industrial panel without changing the part number. At 2 A, this is a control-circuit or instrumentation feeder breaker, not a main distribution device. At 440 V it drops to 25 kA Icu, and at 600 V (if applicable) it falls further; the 6 kA Icn at 400 V under 60898-1 is the lower service rating for domestic-style coordination. For industrial panels, the 60947-2 figures govern, and the 50 kA at 415 V means you can place this downstream of a transformer rated up to about 2 MVA and still maintain selectivity with a larger upstream device. Snap-on DIN rail mount, 6 x 9 mm pitches wide (54 mm). Double terminals top and bottom accept up to 25 mm² rigid or 16 mm² flexible — plenty for a 2 A circuit where you'd typically run 1.5 or 2.5 mm². IP20 finger-safe front; the trip indicator shows clear local signalling.","metaTitle":"Schneider Electric A9F05302 Acti9 iC60N MCB, 2 A, D Curve, 3","metaDescription":"Schneider Electric A9F05302 Acti9 iC60N miniature circuit breaker, 2 A rated current, D curve, 3 poles, 50 kA Icu at 415 V AC, DIN rail mount, current production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"2 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6a69876b7668773a631e53b784608ff2.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05302/miniature-circuit-breaker-mcb-acti9-ic60n-3p-2a-d-curve-6000a-iec-608981-50ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05302/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F05302 at 415 V?","answer":"50 kA Icu at 380…415 V AC per EN/IEC 60947-2, and 6 kA Icn at 400 V per EN/IEC 60898-1."},{"question":"What does the D curve mean on this 2 A breaker?","answer":"The D curve trips magnetically at 12 x In (24 A) ±20%, so it tolerates the high inrush of small transformers, solenoid banks, or motor starters without nuisance tripping."},{"question":"Where can I buy A9F05302 and how is it quoted?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What compliance documentation is available for A9F05302?","answer":"The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1 is also listed. For specific RoHS, REACH, or UL documentation, the manufacturer's product compliance portal provides the declarations."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05302","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05302 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}