{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05310","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05310","canonicalUrl":"https://aoctrl.com/schneider/A9F05310","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05310","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05310, miniature circuit-breaker, 3P, 10 A rated, curve D, 36 kA Icu at 12-133 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The A9F05310 is a Schneider Electric Acti9 iC60N miniature circuit-breaker, 3-pole, rated 10 A with a D tripping curve. The thermal-magnetic trip unit handles overloads and short-circuits in distribution panels. This MCB carries a 36 kA Icu at 12–133 V AC (EN/IEC 60947-2), 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V. For a 400 V distribution board, the 10 kA Icu gives you selectivity headroom downstream of a larger upstream breaker. The Icn rating under EN/IEC 60898-1 is 6000 A at 400 V — the standard domestic-breaking figure, but this part is dual-certified so you can spec it for industrial panels where the higher Icu matters. IP20 finger-safe front; no washdown rating, so keep it inside the enclosure. The toggle switch gives visual trip indication and manual on/off control. Listed as current-production (active lifecycle). The Acti9 iC60N series is Schneider's standard distribution MCB line — widely specified, no end-of-life notice.","metaTitle":"A9F05310 Acti9 iC60N Miniature Circuit-Breaker, 10 A, Curve","metaDescription":"A9F05310 Acti9 iC60N MCB, 10 A rated, curve D, 36 kA Icu at 12-133 V AC. Dual-certified to EN/IEC 60947-2 and 60898-1. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cf582c73ab45635768653db53234ec4d.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05310/miniature-circuit-breaker-mcb-acti9-ic60n-3p-10a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05310/alternatives.json"},"ai":{"faq":[{"question":"What is A9F05310's breaking capacity at 400 V?","answer":"At 380–415 V AC the Icu is 10 kA per EN/IEC 60947-2; the Icn under EN/IEC 60898-1 is 6000 A at 400 V."},{"question":"What is A9F05310 used for?","answer":"It is a 10 A, curve D miniature circuit-breaker for distribution panels, sized for circuits with high inrush — motor starters, transformers, welding supplies — where the D curve's 12 x In magnetic trip avoids nuisance tripping."},{"question":"Where can I buy A9F05310?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — send your quantity for a firm offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05310","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05310 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}