{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05325","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05325","canonicalUrl":"https://aoctrl.com/schneider/A9F05325","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05325","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, 25 A, D curve, 3-pole, 36 kA breaking capacity, dual-standard EN/IEC 60947-2 & 60898-1, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F05325 is an Acti9 iC60N miniature circuit breaker — a 25 A, D-curve, 3-pole unit rated for both AC and DC networks. Its 36 kA Icu at 12–133 V AC and 20 kA at 220–240 V AC mean it handles high prospective fault currents on distribution boards without needing an upstream current-limiting fuse. ## Dual-standard rating and what it means for your panel This breaker carries both EN/IEC 60898-1 (the MCB standard for household and similar installations) and EN/IEC 60947-2 (the industrial standard for circuit breakers). The 60898-1 rating gives you the 6 kA Icn at 400 V AC — the standard domestic/small-commercial fault level. The 60947-2 rating goes higher: 10 kA Icu at 380–415 V AC and 36 kA at low voltage. ## DIN-rail footprint and panel integration Snaps onto standard DIN rail — 6 x 9 mm pitches wide (54 mm), 91 mm tall, 78.5 mm deep. That 78.5 mm depth is shallow enough to clear most standard gland plates and enclosure backwalls. The toggle and trip indicator are front-facing; you can read the tripped state through the enclosure window without opening the door.","metaTitle":"Schneider Electric A9F05325 Acti9 iC60N MCB, D Curve, 25 A,","metaDescription":"Schneider Electric A9F05325 Acti9 iC60N miniature circuit breaker, 25 A, D curve, 3-pole, 36 kA breaking capacity, dual-rated EN/IEC 60947-2 & 60898-1. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cd1467c20cd4ff4ec7d21178fddba948.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05325/miniature-circuit-breaker-mcb-acti9-ic60n-3p-25a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05325/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does the A9F05325 carry?","answer":"The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries IP20 finger protection, tropicalisation class 2 per IEC 60068-1, and suitability for isolation per both standards. Specific RoHS/REACH declarations are part of the Schneider Electric compliance pack available on request."},{"question":"What is the A9F05325's depth?","answer":"78.5 mm — shallow enough to clear most standard enclosure backwalls and gland plates when mounted on DIN rail."},{"question":"Where can I buy the A9F05325 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05325","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05325 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}