{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05363","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05363","canonicalUrl":"https://aoctrl.com/schneider/A9F05363","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05363","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit breaker, 63 A, 3P, D curve, 36 kA Icu breaking capacity, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F05363 is an Acti9 iC60N miniature circuit breaker rated for 63 A on a 3-pole configuration with a D tripping curve. It carries a 36 kA Icu breaking capacity at 12–133 V AC, stepping down to 10 kA Icu at 380–415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V AC per EN/IEC 60898-1. At 400 V AC, the A9F05363 delivers 10 kA Icn under EN/IEC 60898-1 and 10 kA Icu under EN/IEC 60947-2. That Icu figure is the same at 380–415 V AC, so the part holds its interrupting rating across the common European low-voltage distribution band. For a panel builder coordinating downstream MCBs with an upstream molded-case or air circuit breaker, that 10 kA at 400 V gives a solid selectivity window — the iC60N will clear a fault before the upstream device sees it, provided the upstream breaker's instantaneous trip is set above 10 kA. The A9F05363 carries a current lifecycle status from Schneider Electric. It is an active catalog item within the Acti9 range, which means it remains a standard BOM line for new panel designs and replacement spares. IP20 rated, so it lives inside an enclosure — no washdown exposure. The toggle actuator and trip indicator provide local visual status, and the contact position indicator confirms isolation suitability per both EN/IEC 60898-1 and 60947-2.","metaTitle":"Schneider Electric A9F05363 Acti9 iC60N MCB, 63 A, 3P, D Cur","metaDescription":"Schneider Electric A9F05363 Acti9 iC60N miniature circuit breaker, 63 A, 3-pole, D curve, 36 kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0a29b234356e5a45b969e53df4dc4191.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05363/miniature-circuit-breaker-mcb-acti9-ic60n-3p-63a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05363/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9F05363?","answer":"The A9F05363 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the A9F05363 at 400 V AC?","answer":"At 400 V AC, the A9F05363 delivers 10 kA Icn per EN/IEC 60898-1 and 10 kA Icu per EN/IEC 60947-2."},{"question":"What does the D curve on the A9F05363 mean?","answer":"The D curve means the magnetic trip threshold is 12 x In ±20%, so the breaker will hold through the high inrush currents typical of motor starting, small transformers, or discharge lighting without nuisance tripping."},{"question":"What standards does the A9F05363 comply with?","answer":"The A9F05363 is certified to EN/IEC 60947-2 and EN/IEC 60898-1, covering both industrial and residential installation applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05363","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05363 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}