{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05416","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05416","canonicalUrl":"https://aoctrl.com/schneider/A9F05416","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05416","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05416, miniature circuit-breaker, 4P, 16 A, D curve, 36 kA Icu at 12-133 V AC, DIN rail mount.","salesMarkdown":"The A9F05416 is a Schneider Electric Acti9 iC60N miniature circuit-breaker, 4 poles, rated 16 A with a D curve. It's built for distribution panels where high inrush loads—motors, transformers, welding gear—need a magnetic trip threshold of 12 x In ±20 % so the breaker doesn't nuisance-trip on startup. Breaking capacity hits 36 kA Icu at 12–133 V AC (EN/IEC 60947-2) and 10 kA Icn at 400 V AC (EN/IEC 60898-1), giving solid fault-clearing headroom for most industrial and commercial mains. The D curve (12 x In magnetic trip) is the key differentiator here—it's sized for loads that draw a brief, high surge on energization, like a 16 A motor or a bank of switched-mode supplies. The 16 A rating is the continuous thermal current (In), so the load should not exceed 16 A steady-state. Breaking capacity of 36 kA Icu at low voltage (12–133 V AC) and 10 kA Icn at 400 V AC means this breaker can safely interrupt a short-circuit fault up to those levels without welding contacts or cascading upstream—critical for selectivity studies in a distribution board. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial), so it's accepted in both worlds—panel builders often spec the 60947-2 rating for SCCR compliance, while the 60898-1 rating covers standard branch-circuit protection. IP20 finger-safe front, but the busbar area is live when installed; isolate upstream before working on it. Trip indicator and contact-position indicator give visual confirmation of state without removing the cover.","metaTitle":"A9F05416 Acti9 iC60N 16A D Curve 4P MCB, 36 kA Breaking Capa","metaDescription":"Schneider Electric A9F05416 Acti9 iC60N miniature circuit-breaker, 16 A rated, D curve, 4 poles, 36 kA Icu at 12-133 V AC. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/db55315f85d6cf408ab5f95226bb1df1.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F05416/miniature-circuit-breaker-mcb-acti9-ic60n-4p-16a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05416/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F05416 and get a price?","answer":"We source the A9F05416 to order against an RFQ. Submit a quote request; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to A9F05416 in the Acti9 family?","answer":"Within the Acti9 iC60N range, the closest alternative would be a different current rating or pole count—e.g., a 20 A or 2P variant. There is no pin-compatible drop-in with identical ratings; the D-curve 4P 16 A combination is specific. For a parametric substitute, look at the iC60H series (higher breaking capacity) or iC60L (limiting class), but verify footprint and terminal compatibility."},{"question":"What compliance documentation does Schneider provide for A9F05416?","answer":"The A9F05416 is certified to EN/IEC 60947-2 and EN/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1. Standard documentation includes a CE declaration of conformity and the manufacturer's datasheet. RoHS and REACH compliance are standard for the Acti9 range, though specific statements should be confirmed from the brand's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05416","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05416 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}