{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F05425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F05425","canonicalUrl":"https://aoctrl.com/schneider/A9F05425","factsUrl":"https://aoctrl.com/api/mcp/products/A9F05425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F05425, 4P miniature circuit breaker, D-curve, 25 A, 36 kA breaking capacity at 230 V AC.","salesMarkdown":"The A9F05425 is a 4-pole miniature circuit breaker from the Acti9 iC60N family, rated 25 A with a D-curve magnetic trip at 12 x In (±20 %). The D-curve means the magnetic trip is set at 10–14 times the rated current — designed for loads with a high inrush current, such as motors, transformers, or welding equipment. The 36 kA Icu at 230 V AC (EN/IEC 60947-2) gives you headroom for high-fault installations; at 400 V AC the breaking capacity is 10 kA Icu and 6 kA Icn (EN/IEC 60898-1). Snap-on DIN rail mounting. Width is 72 mm — that's 8 modules of 9 mm pitch. Depth 78.5 mm, height 91 mm. Double terminals top and bottom accept 1…25 mm² rigid or 1…16 mm² flexible; wire strip length 14 mm, tighten to 2 N·m. IP20 finger-safe front, pollution degree 3. The trip indicator and contact position indicator give clear local status.","metaTitle":"A9F05425 Acti9 iC60N MCB, 4P D-curve 25 A, 36 kA","metaDescription":"A9F05425 Acti9 iC60N miniature circuit breaker, 4-pole, D-curve, 25 A rated current, 36 kA breaking capacity at 230 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/617e18d5b93dde239e8268ca4e22dbbe.pdf","sourceUrl":"https://www.se.com/uk/en/product/A9F05425/miniature-circuit-breaker-mcb-acti9-ic60n-4p-25a-d-curve-6000a-iec-608981-10ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F05425/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F05425 and get a price?","answer":"The A9F05425 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the breaking capacity of A9F05425?","answer":"Breaking capacity is 36 kA Icu at 12…133 V AC, 20 kA Icu at 220…240 V AC, 10 kA Icu at 380…415 V AC, 6 kA Icu at 440 V AC (all per EN/IEC 60947-2), and 10 kA Icn at 400 V AC per EN/IEC 60898-1."},{"question":"What compliance documentation does Schneider provide for A9F05425?","answer":"The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1. The manufacturer provides the usual declaration of conformity and CE marking; RoHS/REACH documentation is available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F05425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F05425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}