{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06120","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06120","canonicalUrl":"https://aoctrl.com/schneider/A9F06120","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06120","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F06120, miniature circuit breaker, 1P, 20 A, B-curve, 42 kA Icu, DIN rail.","salesMarkdown":"The A9F06120 is a 1-pole Acti9 iC60H miniature circuit breaker rated 20 A with a B-curve trip characteristic. The 42 kA Icu at 12…60 V AC (EN/IEC 60947-2) gives you serious fault-clearing headroom on a 20 A branch; the 10 kA Icn at 230 V (EN/IEC 60898-1) is the domestic/commercial rating for that same breaker. Dual-standard certification means it qualifies for both industrial (60947-2) and residential (60898-1) applications, which simplifies BOM consolidation across panel builds. The thermal-magnetic trip unit combines a bimetal for overload protection and a solenoid for short-circuit. ## Integration notes The toggle actuator provides local on/off and a trip-indicator flag for quick fault isolation on the panel face. Depth of 78.5 mm and height of 91 mm mean it clears most standard enclosure gland plates and busbar shrouds.","metaTitle":"A9F06120 Acti9 iC60H MCB, 20 A, 1P, B-Curve, 78.5 mm","metaDescription":"Schneider Electric A9F06120 Acti9 iC60H miniature circuit breaker, 20 A rated, 1-pole, B-curve, 42 kA Icu at 12-60 VAC. DIN rail mount, IP20. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"20 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 15 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d8a4509661e18ebd6b4cd59bfc3217b2.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06120/miniature-circuit-breaker-mcb-acti9-ic60h-1p-20a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06120/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9F06120?","answer":"The A9F06120 is sourced and quoted to order through independent distribution. Availability and current pricing are confirmed at quote time against an RFQ."},{"question":"What is the breaking capacity of the A9F06120?","answer":"The A9F06120 carries a 42 kA Icu at 12…60 V AC (EN/IEC 60947-2), 30 kA Icu at 100…133 V AC, 15 kA Icu at 220…240 V AC, and 10 kA Icn at 230 V (EN/IEC 60898-1). For DC circuits, it's rated 20 kA Icu at 12…60 V DC and 15 kA Icu at 60…72 V DC."},{"question":"What compliance documentation does Schneider provide for the A9F06120?","answer":"The A9F06120 is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation per both standards. It carries IP20 protection (IEC 60529), pollution degree 3, and tropicalisation class 2 (IEC 60068-1)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06120","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06120 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}