{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06132","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06132","canonicalUrl":"https://aoctrl.com/schneider/A9F06132","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06132","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H miniature circuit breaker, A9F06132, 1P, B curve, 32 A rated current, 42 kA Icu breaking capacity at 12-60 VAC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F06132 is an Acti9 iC60H miniature circuit breaker — 1-pole, B-curve, rated 32 A. The B curve (magnetic trip at 4 x In +/-20%) means it handles resistive and light inductive loads well but will nuisance-trip on high inrush currents from motors or transformers; spec it for lighting, heating, or general socket circuits, not motor feeders. At 230 VAC the Icn is 10,000 A per EN/IEC 60898-1, the standard for domestic and commercial distribution boards. The 18 mm width (2 x 9 mm pitches) snaps onto a DIN rail, and the double terminal accepts up to 35 mm² rigid or 25 mm² flexible — sized for a 32 A feed without pigtailing. ## Deployment context The toggle and trip indicator are visible through the enclosure door, so fault isolation doesn't require opening the panel. Pollution degree 3 (conductive pollution, occasional condensation) matches typical industrial environments per IEC 60947-2. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/commercial). Suitability for isolation confirmed under both standards — the contact position indicator shows whether the contacts are open. Overvoltage category IV (for utility-side connection) and tropicalisation class 2 (55°C, 95% RH) per IEC 60068-1. Thermal-magnetic trip unit, no integral earth-leakage protection.","metaTitle":"Schneider Electric A9F06132 Acti9 iC60H MCB, B Curve 32 A 1P","metaDescription":"Schneider Electric A9F06132 Acti9 iC60H miniature circuit breaker, 32 A, 1-pole, B curve, 42 kA breaking capacity. DIN rail mount, current production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 15 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/990b31915ca26a450c6c14c3e4c69c5d.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06132/miniature-circuit-breaker-mcb-acti9-ic60h-1p-32a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06132/alternatives.json"},"ai":{"faq":[{"question":"What is A9F06132's range and series?","answer":"It belongs to the Schneider Electric Acti9 range, iC60 series, iC60H variant — the high-breaking-capacity version of the iC60 family."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06132","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06132 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}