{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06150","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06150","canonicalUrl":"https://aoctrl.com/schneider/A9F06150","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06150","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, 1P, B-curve, 50 A, 10 kA Icn at 230 V AC, DIN rail mount.","salesMarkdown":"## What this MCB carries — and what it clears The A9F06150 is a 1-pole Acti9 iC60H miniature circuit breaker rated 50 A with a B-curve magnetic trip at 4 x In ±20 %. It is listed to both EN/IEC 60947-2 (Category A) and EN/IEC 60898-1, so it can serve distribution panels under either standard — the 60947-2 rating gives the higher short-circuit capacity numbers for industrial coordination studies. Breaking capacity reaches 42 kA Icu at 12–60 V AC, 15 kA Icu at 220–240 V AC, and 10 000 A Icn at 230 V AC under the household standard. The 78.5 mm depth and 18 mm width (2 x 9 mm pitches) fit a standard DIN-rail enclosure; double terminals top and bottom accept up to 35 mm² rigid or 25 mm² flexible. The 18 mm width occupies two 9 mm module pitches — one pole, one unit. Double terminals top and bottom allow through-wiring or daisy-chaining without extra links. Wire stripping length is 14 mm; tightening torque 3.5 N.m. IP20 finger-safe protection applies once installed in an enclosure. ## Standards and approvals — what they certify Dual-rated to EN/IEC 60898-1 (the household standard for MCBs) and EN/IEC 60947-2 (the industrial standard for circuit breakers). The 60947-2 listing gives the higher Icu breaking capacities needed for industrial coordination studies; the 60898-1 listing gives the Icn rating for residential or commercial distribution. Overvoltage category IV (equipment at the origin of the installation, e.g. main panel). Suitability for isolation is confirmed under both standards, meaning the breaker can be used as a disconnecting means when visibly open.","metaTitle":"A9F06150 Acti9 iC60H MCB, 1P B-curve 50 A, 10 kA IEC 60898-1","metaDescription":"Schneider Electric A9F06150 Acti9 iC60H miniature circuit breaker, 1-pole, B-curve, 50 A rated. Complies with EN/IEC 60947-2 and 60898-1. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"50 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 15 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d901191753a9bf2b12ee8b4d4496324d.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06150/miniature-circuit-breaker-mcb-acti9-ic60h-1p-50a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06150/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06150","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06150 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}