{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06250","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06250","canonicalUrl":"https://aoctrl.com/schneider/A9F06250","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06250","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H miniature circuit breaker, A9F06250, 50 A, 2-pole, curve B, 42 kA Icu at 12-133 V AC, DIN rail mount.","salesMarkdown":"The A9F06250 is a Schneider Electric Acti9 iC60H miniature circuit breaker — 50 A rated current, 2-pole, curve B, with a 42 kA Icu breaking capacity at 12-133 V AC. At 220-240 V AC it still holds 30 kA Icu, and at 380-415 V AC it's 15 kA Icu. The curve B magnetic trip (4 x In ±20%) means it trips instantaneously at 200 A (4 × 50 A) — that's a fast, low-threshold trip designed for resistive loads like heaters, lighting banks, and control transformers where inrush is minimal. For motor or drive circuits with higher inrush, a curve C or D would be the better call; this one stays in the distribution and general-purpose zone. The IP20 finger-safe front allows panel-door mounting without additional shrouding. Pollution degree 3 rating means it's suitable for industrial enclosures where conductive dust or humidity is present — no derating needed for typical control-panel environments. Dual-certified to EN/IEC 60947-2 (industrial circuit-breaker standard) and EN/IEC 60898-1 (household/miniature breaker standard) — so it qualifies for both industrial panelboards and commercial distribution boards. Isolation suitability is confirmed under both standards. The thermal-magnetic trip unit provides overload protection via the thermal bimetal and short-circuit protection via the solenoid.","metaTitle":"A9F06250 Acti9 iC60H MCB, 50 A, 2P, Curve B, 42 kA Icu","metaDescription":"A9F06250 Acti9 iC60H miniature circuit breaker, 50 A, 2-pole, curve B, 42 kA Icu at 12-133 V AC. Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"50 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d1506f36294211eb31b8bbc0353d085f.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06250/miniature-circuit-breaker-mcb-acti9-ic60h-2p-50a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06250/alternatives.json"},"ai":{"faq":[{"question":"What is A9F06250's breaking capacity at 400 V?","answer":"At 400 V AC, the A9F06250 has a 15 kA Icu per EN/IEC 60947-2 and a 10 kA Icn per EN/IEC 60898-1. The higher 42 kA rating applies at 12-133 V AC."},{"question":"What is the closest alternative to A9F06250 in the Acti9 range?","answer":"Within the Acti9 iC60 range, the A9F06250 is the 50 A, 2-pole, curve B, high-performance (H) variant. The standard-performance 'N' variant (iC60N) has a lower breaking capacity — typically 6-10 kA Icn — while the 'L' variant (iC60L) offers 15 kA Icn at 400 V. For the same 50 A, 2P, curve B configuration, the iC60N order code would be A9F05250 and the iC60L would be A9F07250. The H variant here splits the difference with 10 kA Icn at 400 V."},{"question":"Where can I buy A9F06250?","answer":"The A9F06250 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06250","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06250 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}