{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06313","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06313","canonicalUrl":"https://aoctrl.com/schneider/A9F06313","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06313","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit-breaker, 3P, 13 A, curve B, breaking capacity 42 kA Icu at 133 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F06313 is an Acti9 iC60H miniature circuit-breaker, 3-pole, rated 13 A with a B-curve trip characteristic. It is designed for distribution boards and sub-distribution panels where the load is primarily resistive or low-inrush, such as lighting circuits or small control transformers. Breaking capacity is the headline here: 42 kA Icu at 12–133 V AC, 30 kA at 220–240 V, 15 kA at 380–415 V, and 10 kA at 440 V, all per EN/IEC 60947-2. That iC60H suffix signals the high-breaking variant — the standard iC60 (no H) tops out at 25 kA at 220–240 V. If your panel's prospective short-circuit current at the busbar exceeds 25 kA, this H version is the one that holds without upstream fuses. The 10 kA Icn at 400 V per EN/IEC 60898-1 covers the domestic/commercial certification path. The 78.5 mm depth leaves clearance for a standard enclosure door with the toggle and trip indicator visible. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible, with a 2 N·m tightening torque. The thermal-magnetic trip unit gives a fixed thermal curve with magnetic pickup at 4 x In ±20 %. Electrical durability is 10,000 cycles, mechanical 20,000 — figure on replacing it after roughly 10 years of daily switching in a lighting panel. IP20 finger-safe terminals; separate earth-leakage block (Vigi iC60) can be added on the downstream side without extra DIN width.","metaTitle":"Schneider Electric A9F06313 Acti9 iC60H MCB, 3P, 13 A, Curve","metaDescription":"Schneider Electric A9F06313 Acti9 iC60H miniature circuit breaker, 3-pole, 13 A, curve B, breaking capacity 42 kA Icu at 133 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9647b4eefa09022f8641d76283b3cde6.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06313/miniature-circuit-breaker-mcb-acti9-ic60h-3p-13a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06313/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F06313?","answer":"The breaking capacity varies by voltage: 42 kA Icu at 12–133 V AC, 30 kA at 220–240 V, 15 kA at 380–415 V, and 10 kA at 440 V, all per EN/IEC 60947-2. It also carries a 10 kA Icn at 400 V per EN/IEC 60898-1."},{"question":"What is the closest alternative to A9F06313 in the same family?","answer":"The standard-breaking iC60N (e.g., A9F06303) is the closest pin-compatible alternative, but its breaking capacity tops out at 25 kA at 220–240 V. If your panel's prospective fault current is below that, the iC60N saves cost; above it, the iC60H (A9F06313) is the correct choice."},{"question":"Where can I buy A9F06313?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment."},{"question":"What compliance documentation does Schneider provide for A9F06313?","answer":"The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries a suitability-for-isolation marking per both standards. The Acti9 range typically includes CE, UKCA, and EAC declarations; specific RoHS/REACH declarations are available from Schneider's documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06313","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06313 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}