{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06410","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06410","canonicalUrl":"https://aoctrl.com/schneider/A9F06410","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06410","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit-breaker, 4P, 10 A, curve B, 42 kA Icu at 133 V AC, DIN rail mount, IP20.","salesMarkdown":"The A9F06410 is a Schneider Acti9 iC60H miniature circuit-breaker (MCB) rated 10 A, 4-pole, curve B. At 400 V AC the Icn is 10 kA per EN/IEC 60898-1, which is the domestic/commercial rating; the higher Icu figures (30 kA at 240 V, 15 kA at 415 V) give the industrial specifier headroom for transformer-fed distribution boards. Curve B means magnetic tripping occurs at 3 to 5 times In (here 30–50 A), suited for resistive or lighting loads with low inrush — not for motor starting, which needs curve C or D. The thermal-magnetic trip unit handles overloads via a bimetal strip and short-circuits via a solenoid, no electronics to fail in high-ambient heat. Snaps onto standard DIN rail. At 72 mm wide (4-pole, 9 mm per pitch × 8 pitches,), it occupies the same footprint as any 4P iC60 — no surprise when swapping into an existing Acti9 board. Depth 78.5 mm clears most 80 mm-deep enclosures; height 91 mm fits standard 120 mm DIN-rail backplates. IP20 finger-safe terminals are fine for enclosed panels; not rated for washdown. Tightening torque 2 N·m; strip length 14 mm. The part carries dual certification to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/commercial), so it qualifies for both IEC 61439 switchboard assemblies and household consumer units. Overvoltage category IV means it can be installed at the service entrance, not just sub-distribution.","metaTitle":"Schneider A9F06410 Acti9 iC60H MCB, 10 A, 4P, Curve B, 42 kA","metaDescription":"Schneider A9F06410 Acti9 iC60H miniature circuit-breaker, 10 A, 4-pole, curve B, 42 kA Icu at 133 V AC. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/12e07c6a94c235389bf99f1fb2a7ccb7.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06410/miniature-circuit-breaker-mcb-acti9-ic60h-4p-10a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06410/alternatives.json"},"ai":{"faq":[{"question":"What is A9F06410's breaking capacity at 400 V?","answer":"At 400 V AC the Icn per EN/IEC 60898-1 is 10 kA; the Icu per EN/IEC 60947-2 is 15 kA at 380–415 V AC and 10 kA at 440 V AC."},{"question":"Where can I buy A9F06410 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What compliance documentation does Schneider provide for A9F06410?","answer":"The MCB is certified to EN/IEC 60947-2 and EN/IEC 60898-1, tropicalised to class 2 per IEC 60068-1, and carries pollution degree 3 per EN/IEC 60947-2. RoHS/REACH declarations are standard for the Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06410","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06410 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}