{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06413","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06413","canonicalUrl":"https://aoctrl.com/schneider/A9F06413","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06413","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F06413, miniature circuit breaker, 4P, 13 A, B-curve, 42 kA Icu at 12-133 V AC, DIN rail.","salesMarkdown":"The A9F06413 is a Schneider Electric Acti9 iC60H miniature circuit breaker rated 13 A with a B-curve trip characteristic, meaning magnetic tripping occurs at 4 x In ±20 %. The 4-pole (4P) configuration breaks all live conductors. Breaking capacity is 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, and 15 kA at 380-415 V AC per EN/IEC 60947-2. Under EN/IEC 60898-1 it carries 15 kA Icn at 400 V AC. The thermal-magnetic trip unit combines a bimetal for overload protection and a solenoid for short-circuit. The IP20 finger-safe terminals accept rigid cable up to 25 mm² or flexible up to 16 mm², with a wire-stripping length of 14 mm and tightening torque of 2 N.m. ## Deployment context The toggle handle and trip indicator give local status without opening the door. The white housing is standard for the Acti9 range, which is often used in commercial building distribution and light-industrial sub-distribution boards across Europe and markets that follow IEC standards.","metaTitle":"Schneider Electric A9F06413 Acti9 iC60H MCB, 13 A, 4P, B-Cur","metaDescription":"Schneider Electric A9F06413 Acti9 iC60H miniature circuit breaker, 13 A rated current, 4 poles, B-curve, 42 kA breaking capacity. DIN rail mount, dual certified EN/IEC 60947-2 and","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/086bcf09af8af38de921bd1c5d36074b.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06413/miniature-circuit-breaker-mcb-acti9-ic60h-4p-13a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06413/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F06413?","answer":"42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, 15 kA at 380-415 V AC per EN/IEC 60947-2, and 15 kA Icn at 400 V AC per EN/IEC 60898-1."},{"question":"What standards does A9F06413 comply with?","answer":"Dual-certified to EN/IEC 60947-2 (industrial MCB standard) and EN/IEC 60898-1 (domestic MCB standard). Also carries suitability for isolation per both standards, pollution degree 3, and overvoltage category IV."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06413","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06413 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}