{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06425","canonicalUrl":"https://aoctrl.com/schneider/A9F06425","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit-breaker, 4P, 25 A, B-curve, 42 kA Icu at 12-133 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F06425 is an Acti9 iC60H miniature circuit-breaker (MCB) rated for 25 A with a B-curve trip characteristic, 4 poles, and a 42 kA Icu breaking capacity at 12-133 V AC. The 60947-2 rating (42 kA Icu at 12-133 V AC, 30 kA at 220-240 V, 15 kA at 380-415 V, 10 kA at 440 V) is the industrial breaking capacity — it tells you the MCB can safely interrupt a fault up to those levels without welding its contacts or exploding. The 60898-1 rating (15 kA Icn at 400 V) is the domestic/commercial rating. The overvoltage category IV and pollution degree 3 ratings mean this MCB is rated for main incoming supply panels, not just sub-distribution. The 4-pole body occupies 8 x 9 mm pitches — 72 mm wide total. Terminals accept 1-25 mm² rigid or 1-16 mm² flexible wire; double terminals on top and bottom allow daisy-chaining without extra distribution blocks. IP20 finger-safe protection means it is for use inside an enclosure, not exposed. The toggle actuator and trip indicator give clear visual status for commissioning and maintenance. ## Environmental and durability Rated for 10,000 electrical cycles and 20,000 mechanical cycles — sufficient for most distribution panels where the MCB is operated infrequently (isolation switching).","metaTitle":"Schneider Electric A9F06425 Acti9 iC60H MCB, 25 A, 4P, B-Cur","metaDescription":"Schneider Electric A9F06425 Acti9 iC60H miniature circuit-breaker, 25 A rated current, 4 poles, B-curve, 42 kA Icu breaking capacity. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/355737074ef4d71abfe5eb008a9594a8.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06425/miniature-circuit-breaker-mcb-acti9-ic60h-4p-25a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06425/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F06425 and what is the lead time?","answer":"The A9F06425 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here."},{"question":"What is the closest alternative to A9F06425 in the Acti9 family?","answer":"Within the Acti9 iC60H range, the closest alternative would be a different current rating or pole count (e.g., a 20 A or 32 A 4P B-curve variant). There is no pin-compatible drop-in with identical ratings; the A9F06425 is the specific 25 A 4P B-curve order code."},{"question":"What is A9F06425's depth?","answer":"The A9F06425 has a depth of 78.5 mm."},{"question":"What compliance standards does A9F06425 meet?","answer":"The A9F06425 is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It is suitable for isolation per both standards, and carries overvoltage category IV and pollution degree 3 ratings."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}