{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06463","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06463","canonicalUrl":"https://aoctrl.com/schneider/A9F06463","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06463","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, 4P, 63 A, B-curve, 42 kA Icu at 12-133 V AC.","salesMarkdown":"The Schneider Electric A9F06463 is a 63 A, 4-pole miniature circuit breaker from the Acti9 iC60H series, with a B-curve trip characteristic. Rated at 63 A, this MCB handles the full load current of a submain or a large branch circuit. The breaking capacity is 42 kA Icu at 12–133 V AC, 30 kA at 220–240 V AC, and 15 kA at 380–415 V AC (per EN/IEC 60947-2). At 400 V AC, the Icn is 15 kA per EN/IEC 60898-1. This dual-rated MCB meets both the industrial (60947-2) and domestic/light commercial (60898-1) standards, so it can be specified in a panel that requires industrial coordination or a residential load center. ## Integration notes Depth is 78.5 mm, height 91 mm. Terminals accept 1–35 mm² rigid or 1–25 mm² flexible conductors; tightening torque is 3.5 N.m.","metaTitle":"Schneider A9F06463 Acti9 iC60H MCB, 63 A, 4P, B-Curve","metaDescription":"Schneider A9F06463 Acti9 iC60H miniature circuit breaker, 63 A rated current, 4 poles, B-curve, 42 kA breaking capacity at 12-133 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/82fa0c0d454f940b9a9c61a10e82a5e6.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06463/miniature-circuit-breaker-mcb-acti9-ic60h-4p-63a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06463/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9F06463?","answer":"Pricing and availability are confirmed at quote time. Submit an RFQ through the storefront; the part is sourced to order through independent distribution."},{"question":"What is the closest pin-compatible alternative to A9F06463 in this component family?","answer":"Within the Acti9 iC60H range, the closest alternative would be a different current rating or curve code — for example, a 63 A C-curve (A9F06464) if you need higher inrush tolerance. All iC60H breakers share the same footprint, terminal layout, and DIN-rail mounting."},{"question":"What compliance documentation does this brand provide for A9F06463?","answer":"The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation. It also meets tropicalisation class 2 per IEC 60068-1. RoHS and REACH declarations are standard for Schneider Electric Acti9 products."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06463","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06463 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}