{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06613","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06613","canonicalUrl":"https://aoctrl.com/schneider/A9F06613","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06613","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H miniature circuit-breaker, A9F06613, 13 A, curve B, 1P+N, 42 kA Icu at 12-60 V AC, DIN-rail mount.","salesMarkdown":"The A9F06613 is a Schneider Electric Acti9 iC60H miniature circuit-breaker (MCB) rated 13 A with a B-curve trip characteristic (magnetic tripping at 4 x In ±20 %). Breaking capacity is 42 kA Icu at 12–60 V AC, 30 kA at 100–133 V AC, and 15 kA at 220–240 V AC per EN/IEC 60947-2, plus 10 000 A Icn at 230 V AC per EN/IEC 60898-1. This dual-standard rating means it can be applied in both industrial (60947-2) and residential/commercial (60898-1) distribution boards, with the 42 kA figure covering low-voltage fault levels typical in industrial control panels. The double terminal accepts 1–25 mm² rigid or 1–16 mm² flexible wire; strip length is 14 mm and tightening torque is 2 N.m. IP20 finger-safe terminals suit enclosed panel installations.","metaTitle":"Schneider Electric A9F06613 Acti9 iC60H MCB, 13 A, Curve B,","metaDescription":"Schneider Electric A9F06613 Acti9 iC60H miniature circuit-breaker, 13 A, curve B, 1P+N, 42 kA Icu at 12-60 V AC. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/af332a2a72b16e077915d972d8dd0309.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06613/miniature-circuit-breaker-mcb-acti9-ic60h-1p+n-13a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06613/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F06613 and how do I get a price?","answer":"The A9F06613 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is A9F06613's listed depth (78.5 mm) on this component line?","answer":"The A9F06613 has a depth of 78.5 mm."},{"question":"What is A9F06613's listed range (Acti9) on this component line?","answer":"The A9F06613 belongs to the Schneider Electric Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06613","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06613 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}