{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06632","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06632","canonicalUrl":"https://aoctrl.com/schneider/A9F06632","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06632","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F06632, miniature circuit breaker, 32 A, B-curve, 1P+N, 15 kA Icu at 240 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F06632 is an Acti9 iC60H miniature circuit breaker rated 32 A with a B-curve trip characteristic, 1P+N configuration, and a 15 kA Icu breaking capacity at 220–240 V AC per EN/IEC 60947-2. The iC60H designation means this breaker's industrial breaking capacity (Icu) is 15 kA at 220–240 V AC, 30 kA at 100–133 V AC, and 42 kA at 12–60 V AC. Under the domestic standard (60898-1) its Icn is 10 kA at 230 V AC. For a 32 A circuit, 15 kA Icu gives solid selectivity headroom upstream of a typical 25 kA or 36 kA main breaker in a distribution board — the fault energy is unlikely to exceed the breaker's interrupt rating before the upstream device clears. The utilisation category is A (no intentional time delay for selectivity), so coordination relies on the upstream device's delay curve, not this breaker's. Snap-on DIN rail mount per EN/IEC 60715. Neutral is on the left, switched pole on the right. Terminals accept double conductors up to 35 mm² rigid or 25 mm² flexible; strip length is 14 mm, tightening torque 3.5 N·m.","metaTitle":"Schneider Electric A9F06632 Acti9 iC60H MCB, 32A B-Curve 1P+","metaDescription":"Schneider Electric A9F06632 Acti9 iC60H miniature circuit breaker, 32 A rated, B-curve, 1P+N, 15 kA Icu at 240 V AC. Dual certified to EN/IEC 60947-2 and 60898-1. Quoted to order a","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/59972efda19b245146d47af9674ffffb.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06632/miniature-circuit-breaker-mcb-acti9-ic60h-1p+n-32a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06632/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does Schneider provide for A9F06632?","answer":"The breaker is dual certified to EN/IEC 60947-2 and EN/IEC 60898-1, carries IP20 per IEC 60529, and is tropicalised to class 2 per IEC 60068-1. Documentation including the declaration of performance and CE declaration is available from Schneider Electric's product documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06632","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06632 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}