{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F06640","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F06640","canonicalUrl":"https://aoctrl.com/schneider/A9F06640","factsUrl":"https://aoctrl.com/api/mcp/products/A9F06640","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F06640, miniature circuit breaker, 40 A, B-curve, 1P+N, 10 kA Icn, DIN rail.","salesMarkdown":"The Schneider Electric A9F06640 is an Acti9 iC60H miniature circuit breaker (MCB) rated at 40 A with a B-curve trip characteristic, 1P+N poles, and a breaking capacity of 10 kA Icn at 230 V AC per EN/IEC 60898-1. The B-curve (4 x In magnetic trip limit, +/- 20%) means this MCB trips instantaneously at 4 times its 40 A rated current, i.e., between 128 A and 192 A. The 1P+N configuration switches the phase and provides a switched neutral, but only the phase pole is protected; the neutral pole is not overcurrent-protected. The left-side neutral position is fixed, so confirm busbar and wiring order before terminating. This MCB is dual-certified to EN/IEC 60898-1 (domestic/similar installation standard, Icn rating) and EN/IEC 60947-2 (industrial standard, Icu rating). It is suitability for isolation per both standards, meaning it can be used as a disconnecting means under load. Overvoltage category IV means it can be installed at the origin of the installation (utility meter side), not just downstream sub-distribution. Mounts on DIN rail and occupies 4 module pitches, each 9 mm, for a total width of 36 mm. Depth is 78.5 mm, height 91 mm. Terminals accept double conductors: 1...35 mm² rigid or 1...25 mm² flexible, with a tightening torque of 3.5 N.m and a wire strip length of 14 mm. IP20 finger-safe terminals suit enclosed panel installation but not washdown environments. The toggle control and trip indicator provide local status without opening the panel door.","metaTitle":"Schneider Electric A9F06640 Acti9 iC60H MCB, 40A B-Curve 1P+","metaDescription":"Schneider Electric A9F06640 Acti9 iC60H miniature circuit breaker, 40 A rated, B-curve, 1P+N, 10 kA Icn per EN/IEC 60898-1. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"40 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"4 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/691c9eecb77cd886dc7286af80c2feef.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F06640/miniature-circuit-breaker-mcb-acti9-ic60h-1p+n-40a-b-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F06640/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F06640 and how do I get a price?","answer":"The A9F06640 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm availability and current pricing."},{"question":"What is A9F06640's breaking capacity at 230 V?","answer":"The A9F06640 has a breaking capacity of 10 kA Icn at 230 V AC per EN/IEC 60898-1, and 15 kA Icu at 220...240 V AC per EN/IEC 60947-2."},{"question":"What compliance documentation does this brand provide for A9F06640?","answer":"The A9F06640 is certified to EN/IEC 60898-1 and EN/IEC 60947-2, and is suitability for isolation per both standards. It carries IP20 protection and tropicalisation class 2 per IEC 60068-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F06640","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F06640 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}