{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07132","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07132","canonicalUrl":"https://aoctrl.com/schneider/A9F07132","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07132","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F07132, 1P, 32 A, C-curve, 42 kA Icu at 12-60 V AC, thermal-magnetic miniature circuit breaker.","salesMarkdown":"The A9F07132 is a 1-pole Acti9 iC60H miniature circuit breaker rated 32 A with a C-curve magnetic trip (8 x In +/- 20 %). The C-curve means it tolerates moderate inrush — typical for lighting, small motor, and general distribution loads — without nuisance tripping. The 42 kA Icu at 12-60 V AC (EN/IEC 60947-2) gives headroom for high-fault installations; at 230 V AC the Icn is 10 kA per EN/IEC 60898-1, which covers standard domestic and light commercial panel duty. Dual-rated to both the distribution standard (60898-1) and the industrial standard (60947-2), so it qualifies for either spec line without a separate part number. ## Deployment context Snaps onto DIN rail (EN 60715) — 18 mm per pole, so this 1P unit occupies 2 x 9 mm pitches. The IP20 finger-safe terminals accept up to 35 mm² rigid or 25 mm² flexible wire; torque to 3.5 N·m. The toggle handle and trip-indicator flag give local status without opening the panel door.","metaTitle":"Schneider Electric A9F07132 Acti9 iC60H MCB, 32 A, 1P, C-Cur","metaDescription":"Schneider Electric A9F07132 Acti9 iC60H miniature circuit breaker, 32 A rated current, 1-pole, C-curve, 42 kA Icu at 12-60 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 15 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d013478f2cec1cf2d767015e6edfb51e.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07132/miniature-circuit-breaker-mcb-acti9-ic60h-1p-32a-c-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07132/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F07132 at 230 V AC?","answer":"At 230 V AC 50/60 Hz the Icn is 10,000 A per EN/IEC 60898-1. Under the industrial standard EN/IEC 60947-2 the Icu is 15 kA at 220-240 V AC."},{"question":"Where can I buy the A9F07132?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What standards does the A9F07132 comply with?","answer":"It is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation confirmed under both standards. Pollution degree 3 per 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07132","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07132 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}