{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07170","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07170","canonicalUrl":"https://aoctrl.com/schneider/A9F07170","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07170","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, 1P, 0.5 A, C curve, 70 kA Icu at 240 V AC, DIN rail mount.","salesMarkdown":"The A9F07170 is a 1-pole Acti9 iC60H miniature circuit breaker rated at 0.5 A with a C curve (magnetic trip at 8 x In ±20 %). The 70 kA Icu breaking capacity at 240 V AC (per EN/IEC 60947-2) is its real fault-interruption muscle — it can safely interrupt a 70,000 A prospective fault without welding contacts or exploding the case. That rating matters if this breaker sits downstream of a large transformer or in a high-fault-capacity panel; the 10,000 A Icn per EN/IEC 60898-1 is the domestic-standard rating for the same part. Overvoltage category IV and pollution degree 3 mean the breaker is designed for the main distribution board at the service entrance, not just sub-panels. It tolerates the transient overvoltages and conductive dust typical of industrial switchboards. Dual certification to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic) gives it a broader application scope than an MCB carrying only one standard. ## Deployment and integration At 18 mm wide (2 x 9 mm pitches), it occupies one modular space in a distribution board. The double terminals accept 1–25 mm² rigid or 1–16 mm² flexible copper; strip length is 14 mm, tighten to 2 N·m. The toggle handle and trip indicator give local visual status. IP20 finger-safe terminals suit enclosed panels — not for wet or washdown environments.","metaTitle":"Schneider Electric A9F07170 Acti9 iC60H MCB, 0.5 A, 1P, C Cu","metaDescription":"Schneider Electric A9F07170 Acti9 iC60H miniature circuit breaker, 0.5 A rated current, 1P, C curve, 70 kA breaking capacity at 240 V AC. Complies with EN/IEC 60947-2 and 60898-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"0.5 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"70 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 20 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 15 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f7b2feb84a492fe1f8ee661e72810a36.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07170/miniature-circuit-breaker-mcb-acti9-ic60h-1p-0-5a-c-curve-10000a-iec-608981-70ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07170/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9F07170?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is the closest alternative to A9F07170 in the Acti9 iC60 family?","answer":"Within the Acti9 iC60 range, the closest alternative is a variant with a different rated current or curve code. The A9F07170 is a 0.5 A, C-curve, 1-pole unit; a higher-current iC60H (e.g., 1 A or 2 A) shares the same footprint and breaking capacity but changes the thermal trip threshold. No pin-compatible drop-in exists with identical ratings."},{"question":"What compliance documentation does Schneider provide for A9F07170?","answer":"The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries tropicalisation class 2 per IEC 60068-1 and limitation class 3 per EN/IEC 60898-1. Standard documentation includes the manufacturer's declaration of conformity for these standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07170","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07170 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}