{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07302","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07302","canonicalUrl":"https://aoctrl.com/schneider/A9F07302","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07302","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, 3P, C-curve, 2 A, 70 kA Icu, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F07302 is a 3-pole Acti9 iC60H miniature circuit breaker with a C-curve, rated at 2 A. It is a thermal-magnetic trip unit designed for distribution applications in AC or DC networks. This breaker carries a 70 kA Icu at 220...240 V AC and at 380...415 V AC per EN/IEC 60947-2. At 440 V AC the Icu drops to 50 kA, and under the EN/IEC 60898-1 standard its Icn (rated short-circuit capacity) is 10 kA at 400 V AC. The Icn of 10 kA is the value used for domestic/similar installations. It is also rated for isolation — you can use it as a disconnecting means, verified by the contact position indicator that shows when the contacts are open. ## Mounting and integration — DIN rail fit The 3-pole body takes 6 x 9 mm pitches, so the occupied width is 54 mm. Depth is 78.5 mm, height 91 mm. IP20 finger-safe terminals — fine inside a closed panel, not for wet locations. The white colour is standard for the Acti9 range. Lifecycle stage is current — this is an active, in-production part from Schneider Electric's Acti9 family. Pollution degree 3 means it is rated for the conductive environment inside a typical industrial panel. Overvoltage category IV confirms it can be used at the service entrance or main distribution board. Earth-leakage protection is a separate block — this MCB alone does not provide GFCI; pair it with a Vigic iC60 if needed.","metaTitle":"Schneider Electric A9F07302 Acti9 iC60H MCB, 3P C-Curve 2A,","metaDescription":"Schneider Electric A9F07302 Acti9 iC60H miniature circuit breaker, 3-pole, C-curve, 2 A rated current, 70 kA Icu breaking capacity. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"2 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/40ae8294c9e71fe98e6a40a8999b6738.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07302/miniature-circuit-breaker-mcb-acti9-ic60h-3p-2a-c-curve-10000a-iec-608981-70ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07302/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9F07302 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."},{"question":"What is the A9F07302's breaking capacity?","answer":"It has a 70 kA Icu at 220...240 V AC and at 380...415 V AC per EN/IEC 60947-2, dropping to 50 kA Icu at 440 V AC, and an Icn of 10 kA at 400 V AC per EN/IEC 60898-1."},{"question":"What compliance documentation does Schneider provide for the A9F07302?","answer":"The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1, rated for isolation, and carries IP20 protection. Pollution degree 3 and overvoltage category IV are specified. For RoHS/REACH declarations, refer to Schneider Electric's product compliance portal using the order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07302","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07302 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}