{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07350","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07350","canonicalUrl":"https://aoctrl.com/schneider/A9F07350","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07350","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit-breaker, 3P, 50 A, C-curve, 42 kA Icu at 133 V AC, DIN rail.","salesMarkdown":"The A9F07350 is a Schneider Acti9 iC60H miniature circuit-breaker — 3-pole, 50 A rated current, C-curve trip (magnetic trip at 8 x In ±20 %). The 42 kA Icu at 133 V AC (per EN/IEC 60947-2) is the maximum fault current it can safely interrupt at that voltage; at 400 V AC the Icu drops to 15 kA, and the Icn (service breaking capacity per EN/IEC 60898-1) is 10 kA at 400 V. The thermal-magnetic trip handles overloads (thermal bimetal) and short-circuits (solenoid) in one unit — no separate block needed for those two functions, though earth-leakage protection requires a separate Vigi block. The toggle gives local on/off and a trip-indicator flag shows the breaker has tripped even if the handle is reset. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household and similar) — so it qualifies for both commercial and light-industrial installations. The IEC 60898-1 rating is the one that gives you the 10 kA Icn at 400 V; the 60947-2 rating gives the higher Icu values for industrial duty. The brand provides standard RoHS/REACH declarations on request.","metaTitle":"A9F07350 Acti9 iC60H MCB 3P C-Curve 50 A, 42 kA Icu","metaDescription":"A9F07350 is a Schneider Electric Acti9 iC60H miniature circuit-breaker, 3-pole, 50 A, C-curve, 42 kA Icu at 133 V AC. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"50 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/822183d9786300a628eaee0a7e409b2e.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07350/miniature-circuit-breaker-mcb-acti9-ic60h-3p-50a-c-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07350/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9F07350?","answer":"Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution."},{"question":"What is the depth of the A9F07350?","answer":"The A9F07350 has a depth of 78.5 mm, which fits standard Acti9 enclosures and leaves room for wiring and busbar connections."},{"question":"What compliance documentation does this brand provide for A9F07350?","answer":"The brand provides standard RoHS and REACH declarations on request. The part carries dual certification to EN/IEC 60947-2 and EN/IEC 60898-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07350","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07350 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}