{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07363","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07363","canonicalUrl":"https://aoctrl.com/schneider/A9F07363","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07363","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F07363, miniature circuit breaker, 3-pole, 63 A, C-curve, 15 kA Icn at 400 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F07363 is an Acti9 iC60H miniature circuit breaker rated at 63 A with a C-curve trip characteristic and 3 protected poles. ## Breaking capacity — what 15 kA at 400 V means for selectivity This breaker carries a 15 kA Icu at 380...415 V AC and a 10 kA Icu at 440 V AC per EN/IEC 60947-2, plus a 10 kA Icn at 400 V AC per EN/IEC 60898-1. The dual certification (60947-2 for industrial and 60898-1 for household/commercial) gives flexibility to use it in either context, though the 60898-1 rating is the lower of the two at 10 kA. ## DIN rail integration and wiring IP20 finger-safe terminals are standard for enclosed panels; no washdown rating here, so keep it behind a gland plate. The toggle actuator and trip indicator give local visual status without opening the panel door. Overvoltage category IV means it's rated for installation at the origin of the installation (utility side of the main panel).","metaTitle":"Schneider Electric A9F07363 Acti9 iC60H MCB, 63 A, 3P, C-Cur","metaDescription":"Schneider Electric A9F07363 Acti9 iC60H miniature circuit breaker, 63 A rated current, 3-pole, C-curve, 15 kA at 400 V. Dual certified to EN/IEC 60947-2 and 60898-1. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/60a24f5008f941c97ee18e0380e85c68.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07363/miniature-circuit-breaker-mcb-acti9-ic60h-3p-63a-c-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07363/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for A9F07363?","answer":"Submit an RFQ through this listing. The part is sourced through independent distribution channels; availability and current pricing are confirmed at quote time."},{"question":"What is the closest alternative to A9F07363 in the Acti9 family?","answer":"Within the Acti9 iC60 range, the key variant difference is the curve code (B, C, or D) and the breaking capacity class (iC60N vs iC60H vs iC60L). The A9F07363 is the iC60H, 63 A, C-curve, 3-pole variant. A B-curve version (same rating and poles) would trip faster on inrush and is better for resistive loads; a D-curve version would tolerate higher inrush for heavy motor or transformer loads. No pin-compatible drop-in exists because the curve is a functional characteristic, not a mechanical one — all iC60 breakers share the same DIN-rail footprint and terminal layout."},{"question":"What is A9F07363's listed depth?","answer":"The A9F07363 has a depth of 78.5 mm."},{"question":"What is A9F07363's range?","answer":"It belongs to the Schneider Electric Acti9 range."},{"question":"What compliance documentation does Schneider provide for A9F07363?","answer":"The breaker is dual certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries pollution degree 3, overvoltage category IV, and tropicalisation class 2 per IEC 60068-1. Suitability for isolation is confirmed under both standards. RoHS and REACH compliance documentation is standard for the Acti9 range."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07363","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07363 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}