{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07402","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07402","canonicalUrl":"https://aoctrl.com/schneider/A9F07402","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07402","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, 4P, 2 A, C curve, 70 kA Icu at 415 V AC, DIN rail mount.","salesMarkdown":"It's a 4-pole unit (4P) that protects all four poles, suited for distribution applications in final subcircuits where the inrush from small motor loads or capacitive loads needs a moderate delay before the magnetic trip — the C-curve's 8 x In +/- 20% magnetic tripping limit handles that. Breaking capacity is 70 kA Icu at 12...133 V AC, 70 kA at 220...240 V AC, and 70 kA at 380...415 V AC per EN/IEC 60947-2. At 440 V AC it holds 50 kA Icu. Snaps onto a DIN rail — 9 mm pitch occupies 8 modules (72 mm wide). Height is 91 mm, depth 78.5 mm. The double terminals top and bottom accept 1...25 mm² rigid or 1...16 mm² flexible cable; tightening torque is 2 N·m. Dual-rated to EN/IEC 60898-1 (the household-breaker standard) and EN/IEC 60947-2 (the industrial standard). That dual rating is what gives it the 10 kA Icn for domestic use and the 70 kA Icu for industrial coordination. Suitability for isolation is confirmed under both standards — the contact position indicator shows open/closed state visually.","metaTitle":"Schneider Electric A9F07402 Acti9 iC60H MCB, 2A Curve C, 4P,","metaDescription":"Schneider Electric A9F07402 Acti9 iC60H miniature circuit breaker, 2A rated current, C-curve, 4-pole, 70kA breaking capacity at 415V AC. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"2 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a300a1b03aa7474799914f9216643162.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07402/miniature-circuit-breaker-mcb-acti9-ic60h-4p-2a-c-curve-10000a-iec-608981-70ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07402/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07402","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07402 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}