{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07406","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07406","canonicalUrl":"https://aoctrl.com/schneider/A9F07406","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07406","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H miniature circuit-breaker, A9F07406, 4P, 6 A rated, C-curve, 42 kA Icu at 12-133 V AC, DIN-rail mount.","salesMarkdown":"## What this MCB delivers for your distribution board The Schneider A9F07406 is a 4-pole miniature circuit-breaker from the Acti9 iC60H series, rated 6 A with a C-curve trip characteristic. The 4-pole configuration (4P) protects all live conductors, including the neutral, in a single module. Breaking capacity is specified per voltage: 42 kA Icu at 12–133 V AC, 30 kA at 220–240 V, 15 kA at 380–415 V, and 10 kA at 440 V AC — the 10 kA Icn at 400 V per EN/IEC 60898-1 is the rating for domestic-style installations. For industrial panels, the Icu figures per EN/IEC 60947-2 govern the SCCR headroom. Thermal-magnetic trip technology with a separate earth-leakage block option means you can add residual-current protection later without swapping the breaker. The unit is rated for isolation (both standards confirm suitability), so it doubles as a disconnector. Overvoltage category IV and pollution degree 3 suit it for main distribution boards near the service entrance. ## Integration and wiring details Snap-on DIN-rail mounting, 72 mm wide (8 x 9 mm pitches). Tightening torque 2 N·m, strip length 14 mm. The toggle control and trip indicator provide local status at a glance. IP20 finger-safe terminals, suitable for enclosed panel use.","metaTitle":"Schneider A9F07406 Acti9 iC60H MCB, 6 A C-curve 4P, 42 kA","metaDescription":"Schneider A9F07406 Acti9 iC60H miniature circuit-breaker, 6 A rated, C-curve, 4 poles, 42 kA Icu at 12-133 V AC. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/91769b993c6476b02a49dae8fa0de9fc.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07406/miniature-circuit-breaker-mcb-acti9-ic60h-4p-6a-c-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07406/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F07406 at 400 V?","answer":"At 400 V AC, the Icn per EN/IEC 60898-1 is 10 kA, and the Icu per EN/IEC 60947-2 is 15 kA at 380–415 V and 10 kA at 440 V."},{"question":"Where can I buy A9F07406 and what is the lead time?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does A9F07406 carry?","answer":"It conforms to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1 and IP20 per IEC 60529."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07406","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07406 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}