{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07410","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07410","canonicalUrl":"https://aoctrl.com/schneider/A9F07410","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07410","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H miniature circuit-breaker, A9F07410, 4P, C-curve, 10 A, 42 kA Icu at 12-133 V AC, DIN rail mount.","salesMarkdown":"The A9F07410 is a 4-pole miniature circuit-breaker from the Acti9 iC60H family, rated 10 A with a C-curve trip characteristic. It's built for distribution panels where you need overcurrent protection on a 4-wire (3-phase + neutral) circuit. Breaking capacity is the headline: 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V, 15 kA at 380-415 V, and 10 kA at 440 V (all per EN/IEC 60947-2). That's a high-interrupting rating for a 10 A MCB — it can clear a fault on a strong transformer-fed bus without welding its contacts. The 15 kA Icn at 400 V per EN/IEC 60898-1 is the standard domestic/commercial rating, but the 60947-2 figures give you the industrial SCCR headroom for panel coordination studies. Snaps onto a DIN rail (mounting support: DIN rail per). It takes 8 modules of 9 mm pitch (72 mm wide), so plan your enclosure rail space accordingly — that's a 4-pole breaker in a standard 72 mm footprint. Height is 91 mm, depth 78.5 mm; the toggle and trip indicator are on the front face. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/commercial). That means it qualifies as a circuit-breaker for isolation (suitability for isolation: yes per both standards). Pollution degree 3, overvoltage category IV — rated for the harsh electrical environment at the service entrance or main distribution board.","metaTitle":"A9F07410 Acti9 iC60H MCB, 4P C-curve 10 A, 42 kA","metaDescription":"A9F07410 Acti9 iC60H miniature circuit-breaker, 4 poles, C-curve, 10 A rated current. Breaking capacity 42 kA Icu at 12-133 V AC. DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"8","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c9d705e358466e394bb208e6d94548f9.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07410/miniature-circuit-breaker-mcb-acti9-ic60h-4p-10a-c-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07410/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F07410 and how do I get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for quote to confirm availability and current pricing."},{"question":"What is A9F07410's breaking capacity at 400 V?","answer":"At 400 V AC, the breaking capacity is 15 kA Icu per EN/IEC 60947-2 and 10 kA Icn per EN/IEC 60898-1."},{"question":"What is the C-curve magnetic trip threshold on this MCB?","answer":"The magnetic tripping limit is 8 x In +/- 20 %, so for a 10 A breaker, the magnetic trip occurs between 64 A and 96 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07410","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07410 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}