{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07604","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07604","canonicalUrl":"https://aoctrl.com/schneider/A9F07604","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07604","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, A9F07604, 4 A, 1P+N, curve C, 70 kA Icu at 240 V AC, DIN rail.","salesMarkdown":"## What this MCB does on the rail The Schneider Electric A9F07604 is an Acti9 iC60H miniature circuit breaker rated 4 A, 1P+N, curve C, with a breaking capacity of 70 kA Icu at 220...240 V AC 50/60 Hz per EN/IEC 60947-2 and 10 kA Icn at 230 V AC per EN/IEC 60898-1. That 70 kA Icu figure means it handles high fault currents typical in industrial distribution panels without upstream coordination headaches — you can land it downstream of a transformer or a main breaker rated up to that level. The thermal-magnetic trip unit gives magnetic tripping at 8 x In +/- 20 %, so it clears short-circuit faults fast while riding through motor inrush on C-curve. Mounts on DIN rail, takes 4 module pitches (9 mm each), and the double terminals accept up to 25 mm² rigid or 16 mm² flexible — enough for a 4 A feeder in a control cabinet. Overvoltage category IV suits main incoming panels. IP20 finger-safe terminals.","metaTitle":"Schneider Electric A9F07604 Acti9 iC60H MCB, 4 A, 1P+N, Curv","metaDescription":"Schneider Electric A9F07604 Acti9 iC60H miniature circuit breaker, 4 A rated, 1P+N, curve C, 70 kA Icu at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"4 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"70 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/524dfae5815f92ddf5098fb7699c42e8.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07604/miniature-circuit-breaker-mcb-acti9-ic60h-1p+n-4a-c-curve-10000a-iec-608981-70ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07604/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F07604?","answer":"70 kA Icu at 220...240 V AC per EN/IEC 60947-2, and 10 kA Icn at 230 V AC per EN/IEC 60898-1."},{"question":"What is the rated current and curve of A9F07604?","answer":"4 A, curve C."},{"question":"What mounting and terminal specs does A9F07604 have?","answer":"DIN rail mount, 4 module pitches, double terminals accepting up to 25 mm² rigid or 16 mm² flexible."},{"question":"Where can I buy A9F07604?","answer":"Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07604","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07604 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}