{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07640","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07640","canonicalUrl":"https://aoctrl.com/schneider/A9F07640","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07640","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F07640, miniature circuit breaker, 40 A, C-curve, 1P+N, 15 kA Icu at 230 V AC, DIN rail.","salesMarkdown":"The Schneider Electric A9F07640 is an Acti9 iC60H miniature circuit breaker rated 40 A with a C-curve (magnetic trip at 8 x In ±20 %). Breaking capacity is 15 kA Icu at 220…240 V AC per EN/IEC 60947-2, and 10 000 A Icn at 230 V AC per EN/IEC 60898-1; that 15 kA Icu figure is the one that governs fault-clearing ability on a 230 V distribution board. Dual-rated to both the 60947-2 (industrial) and 60898-1 (domestic/similar) standards, so it qualifies for commercial panel builds and residential final circuits alike. The thermal-magnetic trip unit combines a bimetal element for overload protection and a solenoid for short-circuit response. With 1 protected pole plus switched neutral (1P+N), it interrupts the live conductor only; the neutral pole switches but does not protect. Snaps onto a DIN rail — standard 36 mm width per pole, 4 module pitches (9 mm each). The double terminal accepts up to 35 mm² rigid or 25 mm² flexible on top or bottom, with a stripping length of 14 mm and a tightening torque of 3.5 N·m. That wire range covers most distribution cable sizes up to 6 AWG equivalent, so it fits both panel feed and load-side wiring without adapters. The toggle actuator gives a clear visual trip indication via the contact position indicator, and the local signalling flag confirms the tripped state even if the toggle is manually reset.","metaTitle":"Schneider Electric A9F07640 Acti9 iC60H MCB, 40 A, C-Curve,","metaDescription":"Schneider Electric A9F07640 Acti9 iC60H miniature circuit breaker, 40 A rated current, C-curve, 1P+N, 15 kA Icu at 230 V AC, DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"40 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/62a04b123d56cd37ebe3d61ca1a29f33.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07640/miniature-circuit-breaker-mcb-acti9-ic60h-1p+n-40a-c-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07640/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F07640 at 230 V?","answer":"At 220…240 V AC, the breaking capacity is 15 kA Icu per EN/IEC 60947-2 and 10 000 A Icn per EN/IEC 60898-1. The 15 kA figure is the industrial rating that governs fault clearing in commercial panel applications."},{"question":"Where can I buy A9F07640?","answer":"The A9F07640 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for A9F07640?","answer":"The A9F07640 is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with IP20 per IEC 60529 and tropicalisation class 2 per IEC 60068-1. Standard Schneider declarations of conformity cover CE and UKCA marking for EU/UK markets."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07640","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07640 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}