{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F07670","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F07670","canonicalUrl":"https://aoctrl.com/schneider/A9F07670","factsUrl":"https://aoctrl.com/api/mcp/products/A9F07670","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, 0.5 A, C-curve, 1P+N, 70 kA breaking capacity, DIN rail, white.","salesMarkdown":"The Schneider A9F07670 is an Acti9 iC60H miniature circuit breaker — a 1P+N unit rated at 0.5 A with a C-curve, designed for distribution boards on DIN rail. The 10 kA Icn per EN/IEC 60898-1 covers the domestic/commercial rating side. Dual-standard certification means it satisfies both the industrial (60947-2) and installation (60898-1) standards, so it works in mixed environments without a coordination headache. At 0.5 A rated current (In), this is a low-current MCB — it protects a control transformer primary, a small power supply, or a signal-loop feeder, not a motor or a general-purpose socket circuit. The C-curve (magnetic trip at 8 x In ±20 %, so 4 A nominal) means it tolerates moderate inrush without nuisance tripping, which suits transformer or capacitive loads. The thermal-magnetic trip unit gives both overload (thermal bimetal) and short-circuit (solenoid) protection in one package. The 10 kA Icn per EN/IEC 60898-1 is the standard domestic rating; the 70 kA figure is what the industrial spec calls for. The 1P+N configuration puts the neutral on the left, switched with the phase.","metaTitle":"Schneider A9F07670 Acti9 iC60H MCB, 0.5 A C-curve, 70 kA","metaDescription":"Schneider A9F07670 Acti9 iC60H miniature circuit breaker, 0.5 A rated, C-curve, 70 kA breaking capacity, 1P+N, DIN rail. Active lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Neutral position":"Left","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"1P + N","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"0.5 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"70 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0ae5830ec8ba09b8511d7bdc9772c4f9.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F07670/miniature-circuit-breaker-mcb-acti9-ic60h-1p+n-0-5a-c-curve-10000a-608981-70ka-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F07670/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F07670 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is A9F07670's listed depth?","answer":"The depth is 78.5 mm, which fits standard DIN-rail enclosures with adequate wiring space behind the rail."},{"question":"What compliance documentation does this brand provide for A9F07670?","answer":"The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with IP20 per IEC 60529, pollution degree 3 per EN/IEC 60947-2, and tropicalisation class 2 per IEC 60068-1. Isolation suitability is confirmed per both standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F07670","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F07670 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}