{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F08202","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F08202","canonicalUrl":"https://aoctrl.com/schneider/A9F08202","factsUrl":"https://aoctrl.com/api/mcp/products/A9F08202","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F08202, miniature circuit breaker, 2 A rated, D curve, 2-pole, 70 kA breaking capacity at 415 V AC, DIN rail mount.","salesMarkdown":"The A9F08202 is a 2 A rated, D-curve miniature circuit breaker from Schneider Electric's Acti9 iC60H series. The 2 A rating is the continuous thermal current; the thermal-magnetic trip unit protects the downstream conductors and equipment from sustained overloads and short circuits. Breaking capacity is the headline number for this part: 70 kA Icu at 415 V AC (per EN/IEC 60947-2), with an Icn of 10 kA at 400 V (per EN/IEC 60898-1). The 10 kA Icn is the service breaking capacity under the domestic-standard 60898-1 test sequence; the 60947-2 rating governs industrial distribution. Snap-on DIN rail mounting, 36 mm wide (4× 9 mm pitches), 91 mm tall, 78.5 mm deep. Two-pole configuration (2P) with protected poles on both paths. IP20 finger-safe terminals — suitable for enclosed panel installation, not for wet or washdown environments.","metaTitle":"Schneider A9F08202 Acti9 iC60H MCB, 2A D-Curve, 2P, 70kA","metaDescription":"Schneider Electric A9F08202 Acti9 iC60H miniature circuit breaker, 2A rated, D curve, 2-pole, 70 kA breaking capacity at 415 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"2 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/273c27ed57117cdeb8befde4e59c601c.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F08202/miniature-circuit-breaker-mcb-acti9-ic60h-2p-2a-d-curve-10000a-iec-608981-70ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F08202/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F08202 and how do I get a price?","answer":"The A9F08202 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What compliance documentation does Schneider provide for A9F08202?","answer":"The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with IP20 per IEC 60529, tropicalisation class 2 per IEC 60068-1, and suitability for isolation per both standards. The manufacturer provides the standard declaration of conformity and product certificate for these marks."},{"question":"What is A9F08202's listed depth?","answer":"The depth is 78.5 mm."},{"question":"What is the D curve on this breaker for?","answer":"The D curve (magnetic trip at 12× In ±20 %) is designed for circuits with high inrush currents — motor loads, transformers, or welding equipment — where a B or C curve would trip on startup."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F08202","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F08202 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}