{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F08220","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F08220","canonicalUrl":"https://aoctrl.com/schneider/A9F08220","factsUrl":"https://aoctrl.com/api/mcp/products/A9F08220","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, miniature circuit breaker, A9F08220, 20 A, D curve, 2P, 42 kA Icu at 12-133 V AC.","salesMarkdown":"The A9F08220 is a 20 A, D-curve miniature circuit breaker from the Schneider Electric Acti9 iC60H series, built for distribution boards where high inrush loads — motor starts, transformer primaries, capacitor banks — need a magnetic trip that holds past 12× In instead of the typical 5–10× of a C curve. That 12× In magnetic threshold ±20 % means it won't nuisance-trip on a motor's locked-rotor draw, but still clears a hard short fast. The 42 kA Icu at 12–133 V AC is the interrupting rating under IEC 60947-2; at 220–240 V it's still 30 kA, and at 380–415 V it's 15 kA. For the EN 60898-1 reference, the Icn is 10 kA at 400 V — the standard domestic/commercial rating. The 2-pole version protects both line conductors in a single-phase or split-phase circuit, with a separate earth-leakage block available if you need RCD integration. Mounts on DIN rail, 36 mm wide, 91 mm tall, 78.5 mm deep. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/commercial). Overvoltage category IV, pollution degree 3, isolation suitability confirmed per both standards. IP20 finger-safe terminals. ## Integration notes Toggle control with trip indicator and contact position indicator. Electrical durability 10,000 cycles, mechanical 20,000 cycles.","metaTitle":"Schneider Electric A9F08220 Acti9 iC60H MCB, D Curve, 20 A,","metaDescription":"Schneider Electric A9F08220 Acti9 iC60H miniature circuit breaker, 20 A, D curve, 2 poles, 42 kA Icu breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"36 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC DC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"20 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b6c772f709b2cc50cf58b85b1f252036.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F08220/miniature-circuit-breaker-mcb-acti9-ic60h-2p-20a-d-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F08220/alternatives.json"},"ai":{"faq":[{"question":"What is A9F08220's listed depth (78.5 mm) on this component line?","answer":"The depth is 78.5 mm — that's the body depth from the DIN-rail mounting surface to the front of the toggle, not including terminal projections."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F08220","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F08220 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}