{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F08313","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F08313","canonicalUrl":"https://aoctrl.com/schneider/A9F08313","factsUrl":"https://aoctrl.com/api/mcp/products/A9F08313","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F08313, miniature circuit breaker, 13 A, D curve, 3P, 42 kA Icu at 12-133 V AC, thermal-magnetic trip, DIN rail mount.","salesMarkdown":"The A9F08313 is a 13 A D-curve miniature circuit breaker from the Acti9 iC60H series, 3-pole, rated for both AC and DC networks. The D curve means magnetic tripping occurs at 12 x In (156 A) with a +/-20% tolerance — so it handles the inrush of motor loads, transformers, or capacitive banks without nuisance trips on start-up. The 42 kA Icu at 12-133 V AC (EN/IEC 60947-2) is its ultimate breaking capacity; at 220-240 V AC that drops to 30 kA, and at 380-415 V AC to 15 kA. At the distribution-board voltage of 400 V AC, the Icn per EN/IEC 60898-1 is 10 kA — the figure that governs residential and light commercial panel coordination. The thermal-magnetic trip unit covers overload (thermal bimetal) and short-circuit (solenoid) in one package, with a separate earth-leakage block available if needed. Depth is 78.5 mm, height 91 mm — check gland-plate clearance if the enclosure is shallow. Lifecycle stage is current — no end-of-life notice on record. For a BOM freeze or line-down spare, the 13 A D-curve in 3P is a standard catalogue item, so supply continuity is predictable. No official successor exists because none is needed. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/ commercial) — covers both the panel builder's coordination study and the final installation standard. Suitability for isolation confirmed under both standards. Contact position indicator and trip indicator give visual confirmation without opening the panel.","metaTitle":"Schneider Electric A9F08313 Acti9 iC60H MCB, 13 A, D Curve,","metaDescription":"Schneider Electric A9F08313 Acti9 iC60H miniature circuit breaker, 13 A rated current, D curve, 3 poles, 42 kA breaking capacity at 12-133 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"13 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f34405f5daa9f2ee83069dc01ce9ff36.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F08313/miniature-circuit-breaker-mcb-acti9-ic60h-3p-13a-d-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F08313/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this brand provide for A9F08313 (RoHS, REACH, UL, IEC)?","answer":"The part carries dual certification to EN/IEC 60947-2 and EN/IEC 60898-1, overvoltage category IV, pollution degree 3, tropicalisation class 2, and IP20. The evidence does not list RoHS or REACH declarations; contact the storefront for the manufacturer's declaration pack."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F08313","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F08313 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}