{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F08316","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F08316","canonicalUrl":"https://aoctrl.com/schneider/A9F08316","factsUrl":"https://aoctrl.com/api/mcp/products/A9F08316","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H miniature circuit breaker, A9F08316, 3P, 16 A, D curve, 42 kA breaking capacity, DIN-rail mount.","salesMarkdown":"The Schneider Electric A9F08316 is an Acti9 iC60H miniature circuit breaker — 3-pole, 16 A rated current, D-curve trip characteristic, with a 42 kA breaking capacity at 12–133 V AC. It is a thermal-magnetic MCB (Category A per EN/IEC 60947-2) suited for distribution applications where high inrush currents from motor or transformer loads demand a D-curve magnetic trip at 12 x In (±20 %). At 220–240 V AC it still holds 30 kA Icu, and at 380–415 V AC it manages 15 kA Icu. Occupies 6 x 9 mm pitches (54 mm wide) — three poles at 18 mm per pole. Height 91 mm, depth 78.5 mm. Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible; tightening torque 2 N·m. Wire strip length 14 mm. IP20 finger-safe front. Overvoltage category IV (mains entry level). Rated insulation voltage 500 V AC. Electrical durability 10,000 cycles; mechanical durability 20,000 cycles. Earth-leakage protection requires a separate Vigi block — not integrated. Local trip indicator and contact position indicator standard. White colour, toggle control.","metaTitle":"Schneider Electric A9F08316 Acti9 iC60H MCB, 16 A, 3P, D Cur","metaDescription":"Schneider Electric A9F08316 Acti9 iC60H miniature circuit breaker, 16 A, 3-pole, D curve, 42 kA breaking capacity. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"6","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/745d7dd3de7899c0dc6e3e5694b4ab5d.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F08316/miniature-circuit-breaker-mcb-acti9-ic60h-3p-16a-d-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F08316/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F08316?","answer":"42 kA Icu at 12–133 V AC, 30 kA Icu at 220–240 V AC, 15 kA Icu at 380–415 V AC, and 10 kA Icn at 400 V AC per EN/IEC 60898-1."},{"question":"What curve and rated current does A9F08316 have?","answer":"D curve, 16 A rated current (In), with magnetic tripping at 12 x In ±20 %."},{"question":"Where can I buy A9F08316 and how is it quoted?","answer":"The A9F08316 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for A9F08316?","answer":"The MCB is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1 and limitation class 3 per EN/IEC 60898-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F08316","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F08316 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}