{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F08425","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F08425","canonicalUrl":"https://aoctrl.com/schneider/A9F08425","factsUrl":"https://aoctrl.com/api/mcp/products/A9F08425","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H miniature circuit breaker, A9F08425, 25 A rated current, 4 poles, D tripping curve, breaking capacity 42 kA Icu at 12-133 V AC.","salesMarkdown":"The Schneider Electric A9F08425 is an Acti9 iC60H miniature circuit breaker rated for 25 A continuous current across four protected poles, with a D tripping curve that holds 12× In (±20 %) before the magnetic trip fires. The part is dual-rated to EN/IEC 60898-1 (domestic-grade Icn of 10 kA at 400 V AC) and EN/IEC 60947-2 (industrial-grade Icu up to 42 kA at 12-133 V AC), so it qualifies for both residential distribution boards and industrial panel builds. ## Breaking capacity and isolation The iC60H frame delivers 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, and 15 kA at 380-415 V AC per EN/IEC 60947-2. At 400 V AC the IEC 60898-1 Icn is 10 kA. The 4P version isolates all poles simultaneously, with a contact-position indicator and a trip-flag for local signalling. IP20 finger-safe front. The thermal-magnetic trip unit is field-non-adjustable, so the 25 A rating is fixed; earth-leakage protection requires a separate Vigi block.","metaTitle":"Schneider Electric A9F08425 Acti9 iC60H MCB, 25 A, 4P, D Cur","metaDescription":"Schneider Electric A9F08425 Acti9 iC60H miniature circuit breaker, 25 A rated current, 4 poles, D tripping curve. Breaking capacity 42 kA at 12-133 V AC. Complies with EN/IEC 60947","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","[In] rated current":"25 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/971ebb82586ae1cc35a0ebfb827dd1c0.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F08425/miniature-circuit-breaker-mcb-acti9-ic60h-4p-25a-d-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F08425/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the A9F08425?","answer":"The breaking capacity varies by voltage: 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, 15 kA at 380-415 V AC, and 10 kA Icn at 400 V AC per EN/IEC 60898-1."},{"question":"How do I get a price and lead time for the A9F08425?","answer":"Submit an RFQ through the distributor. Pricing and availability are confirmed at quote time — the part is sourced to order against your request."},{"question":"What standards does the A9F08425 comply with?","answer":"It complies with EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic), with suitability for isolation confirmed under both."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F08425","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F08425 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}