{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F08432","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F08432","canonicalUrl":"https://aoctrl.com/schneider/A9F08432","factsUrl":"https://aoctrl.com/api/mcp/products/A9F08432","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60H, A9F08432, miniature circuit breaker, D curve, 32 A rated, 4 poles, 78.5 mm depth, DIN rail mount.","salesMarkdown":"The A9F08432 is a 4-pole Acti9 iC60H miniature circuit breaker rated 32 A with a D tripping curve (12 x In magnetic trip limit). The D curve means it tolerates the high inrush of motor or transformer loads without nuisance tripping — the magnetic trip operates at 12 x In, so a 32 A breaker holds through the starting surge of a 7.5 kW motor on a 400 V line and clears a hard short. The 42 kA Icu at 12–133 V AC and 30 kA at 220–240 V AC (per EN/IEC 60947-2) give headroom for high-fault panels; the 15 kA Icu at 380–415 V AC and 10 kA at 440 V AC cover most European industrial distribution. It also carries a 10 kA Icn at 400 V AC under EN/IEC 60898-1 for domestic/commercial branch circuits. Dual-rated to both standards — you can spec it for IEC 60947-2 industrial duty or IEC 60898-1 residential/commercial, whichever your panel design calls for. The thermal-magnetic trip unit handles overload (thermal bimetal) and short-circuit (magnetic solenoid) in one package. IP20 finger-safe terminals — fine inside a closed cabinet, not for wet environments. Snaps onto standard DIN rail (mounting support: DIN rail). Occupies 8 x 9 mm pitches (72 mm wide) — four pole modules side by side. Depth 78.5 mm, height 91 mm. Tightening torque 3.5 N.m. Wire strip length 14 mm. The toggle actuator and trip indicator give local status without opening the door.","metaTitle":"Schneider Electric A9F08432 Acti9 iC60H MCB, D Curve, 32 A,","metaDescription":"Schneider Electric A9F08432 Acti9 iC60H miniature circuit breaker, D curve, 32 A, 4 poles, 78.5 mm depth. Dual-rated EN/IEC 60947-2 and 60898-1. Current lifecycle stage. Quoted to","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"72 mm","Colour":"White","Height":"91 mm","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"8","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iC60","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60H","Network frequency":"50/60 Hz","Poles description":"4P","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","[In] rated current":"32 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"12 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"4","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bcc3e77fea9bb0f70fe65073fd84bed4.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F08432/miniature-circuit-breaker-mcb-acti9-ic60h-4p-32a-d-curve-10000a-iec-608981-15ka-iec-609472-double-term-/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F08432/alternatives.json"},"ai":{"faq":[{"question":"What is A9F08432's depth?","answer":"The depth is 78.5 mm."},{"question":"What is A9F08432 used for?","answer":"It is a miniature circuit breaker for distribution panels, protecting circuits against overload and short circuits. The D curve suits motor, transformer, and other high-inrush loads."},{"question":"Where can I buy A9F08432?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F08432","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F08432 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}