{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F44110","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F44110","canonicalUrl":"https://aoctrl.com/schneider/A9F44110","factsUrl":"https://aoctrl.com/api/mcp/products/A9F44110","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F44110, miniature circuit-breaker, 10 A, C-curve, 1-pole, 36 kA Icu, 18 mm wide, 78.5 mm deep.","salesMarkdown":"## What it is and key ratings The A9F44110: Snap-in 18 mm wide, 10 A C-curve MCB for Acti9 boards. Thermal-magnetic trip, 36 kA Icu at 10-60 V AC, so it handles substantial fault currents at low voltage. 2-module pitch, 78.5 mm deep – fits standard Acti9 panels. ## Mounting and wiring considerations Clip-on DIN rail mount. Terminal accepts 1-25 mm² rigid or 1-16 mm² flexible. Torque to 2 N.m. Padlockable toggle for lockout/tagout. Declared standards: EN/IEC 60898-1 and EN/IEC 60947-2. Pollution degree 3, overvoltage category IV. IP20 finger-safe.","metaTitle":"Schneider A9F44110 iC60N MCB, 10A C-Curve","metaDescription":"Active production Acti9 iC60N miniature circuit-breaker. 10 A rated, C-curve, thermal-magnetic trip. 36 kA Icu at low voltage. 2-module 18 mm wide. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1 EN/IEC 60947-2","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC/DC","Product name":"Disbo iC60","Mounting mode":"Clip-on","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"Rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 10...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 240 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"IC60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 % at 55 °C","Tightening torque":"2 N.m top or bottom","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Provision for padlocking":"Padlockable","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"12...60 V AC 50/60 Hz 100...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 12...60 V DC 60...72 V DC","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$27.94","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ab7a94ac461626eece1bb51e9d1f919.pdf","sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F44110/alternatives.json"},"ai":{"faq":[{"question":"What range is this breaker from?","answer":"Acti9 range."},{"question":"What compliance standards does it meet?","answer":"EN/IEC 60898-1 and EN/IEC 60947-2, pollution degree 3, overvoltage category IV, IP20."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F44110","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F44110 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}