{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F45403","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F45403","canonicalUrl":"https://aoctrl.com/schneider/A9F45403","factsUrl":"https://aoctrl.com/api/mcp/products/A9F45403","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, miniature circuit-breaker A9F45403, 4P, D curve, 3 A rated, 50 kA breaking capacity at 415 V AC.","salesMarkdown":"The A9F45403 is a Schneider Electric Acti9 iC60N miniature circuit breaker — 4 poles, D curve, 3 A rated current. At 3 A, this is sized for a small motor or control transformer branch, not a main feeder. ## Dual-standard certification and lifecycle Tightening torque 2 N·m. Strip length 14 mm. That covers most panel wiring up to a 4 mm² feed for a 3 A branch. The thermal-magnetic trip unit is non-interchangeable — no field-swap of the trip element, so order the exact rating. Padlockable toggle and a trip indicator (red flag visible when tripped) help the field tech confirm isolation before working downstream. Earth-leakage protection requires a separate vigi block — not integrated.","metaTitle":"Schneider Electric A9F45403 iC60N MCB, D Curve 3 A 4P 50 kA","metaDescription":"Schneider Electric A9F45403 Acti9 iC60N miniature circuit breaker, 3 A rated, D curve, 4 poles, 50 kA breaking capacity at 415 V AC. Dual-rated EN/IEC 60898-1 and 60947-2. Current","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"78.5 mm","Width":"72 mm","Height":"85 mm","Voltage":"12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC","IP Rating":"IP20","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to EN/IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Breaking Capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-35 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category A conforming to EN/IEC 60947-2","Electrical Life Cycles":"10000 cycles","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-35...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b58de923cd13b573bc6cad4d68c47b9a.pdf","sourceUrl":"https://www.se.com/sg/en/product/A9F45403/miniature-circuit-breaker-mcb-acti9-ic60n-disbo-4p-3a-d-curve-6000a-iec-en-608981-50ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F45403/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F45403","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F45403 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}