{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F45470","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F45470","canonicalUrl":"https://aoctrl.com/schneider/A9F45470","factsUrl":"https://aoctrl.com/api/mcp/products/A9F45470","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60N, A9F45470, 4-pole miniature circuit breaker, D-curve, 0.5 A, 50 kA breaking capacity at 415 V AC, clip-on DIN rail mount.","salesMarkdown":"The A9F45470 is a 4-pole Acti9 iC60N miniature circuit breaker (MCB) with a D-curve and a 0.5 A rated current. It clips onto a DIN rail (mounting support: rail, clip-on) and takes up 8 x 9 mm pitches (72 mm wide, 85 mm high, 78.5 mm deep), so you can plan the panel layout precisely. The D-curve means magnetic tripping occurs at 12 x In ±20 % — that is, between roughly 4.8 A and 7.2 A — which suits loads with a high inrush, like small transformers or solenoid valves, not general lighting or resistive heaters. Breaking capacity is the number that decides whether it clears a fault without welding contacts or blowing up the panel. This unit delivers 50 kA Icu at 220…240 V AC and at 380…415 V AC (per EN/IEC 60947-2), and 10 kA Icn at 415 V AC (per EN/IEC 60898-1). The 25 kA Icu at 440 V AC is still high for a 0.5 A frame. The thermal-magnetic trip unit handles the two fault regimes: thermal (overload, slow) and magnetic (short-circuit, instantaneous). The IP20 rating (finger-safe terminals) means it belongs inside a closed panel, not exposed to washdown. For a buyer filling a BOM line: the 0.5 A rating is the unusual spec here — most iC60N breakers start at 1 A or higher. That low current, combined with the D-curve and 4-pole format, makes this a niche part that may not sit on every distributor's shelf.","metaTitle":"A9F45470 Acti9 iC60N MCB, 4P D-curve 0.5A, 50kA","metaDescription":"Schneider Electric A9F45470 Acti9 iC60N miniature circuit breaker, 4-pole, D-curve, 0.5 A rated current. 50 kA breaking capacity at 415 V AC. Clip-on DIN rail mount, thermal-magnet","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Color":"White","Depth":"78.5 mm","Width":"72 mm","Height":"85 mm","Voltage":"12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC","IP Rating":"IP20","Control Type":"Toggle","Product Status":"Active","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to EN/IEC 60947-2","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-35 °C","Temperature Storage":"-40...85 °C","Utilization Category":"Category A conforming to EN/IEC 60947-2","Electrical Life Cycles":"10000 cycles","Mechanical Life Cycles":"20000 cycles","Main Product Or Component Type":"Miniature circuit-breaker","Ambient Air Temperature Operation":"-35...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1bc9fc5b27c67615f10f7fcf020d592b.pdf","sourceUrl":"https://www.se.com/id/en/product/A9F45470/acti9-ic60n-4p-05a-d-miniature-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F45470/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F45470","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F45470 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}