{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F56110","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F56110","canonicalUrl":"https://aoctrl.com/schneider/A9F56110","factsUrl":"https://aoctrl.com/api/mcp/products/A9F56110","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 IKQ, miniature circuit breaker, 1P, 10 A, B curve, 10 kA Icn at 240 V AC, EN/IEC 60898-1.","salesMarkdown":"The Schneider Electric A9F56110 is a 1-pole Acti9 IKQ miniature circuit breaker (MCB) rated 10 A with a B tripping curve, designed for AC networks at 240 V and 50/60 Hz. Rated breaking capacity (Icn) is 10,000 A at 240 V AC per EN 60898-1; the service breaking capacity (Ics) is 7,500 A at the same voltage. That Ics figure matters for selectivity coordination downstream — if you're feeding this breaker from a larger upstream device, the 7.5 kA Ics tells you how much fault current it can clear repeatedly without degrading the unit. The limitation class is 3 per EN 60898-1, meaning it limits let-through energy on a high fault — helps protect downstream wiring and connected equipment. Depth is 78.5 mm, height 85 mm. That's a standard MCB footprint — fits any Acti9 distribution board or generic enclosure. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible on the bottom connection; strip length is 14 mm, torque to 2 N·m. Padlockable toggle for lockout/tagout. Rated insulation voltage 440 V AC. Electrical durability 10,000 cycles, mechanical 20,000 cycles.","metaTitle":"Schneider Electric A9F56110 Acti9 IKQ MCB, 10 A, B Curve, 10","metaDescription":"Schneider Electric A9F56110 Acti9 IKQ miniature circuit breaker, 10 A rated, B curve, 10 kA breaking capacity per EN 60898-1. 1P, 240 V AC, thermal-magnetic trip. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"B","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"IKQ","Mounting mode":"Plug-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"Rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to EN 60898-1","Network frequency":"50/60 Hz","Poles description":"1P","Tightening torque":"2 N.m bottom","[In] rated current":"10 A","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Single terminal (bottom) 1...25 mm² rigid Single terminal (bottom) 1...16 mm² flexible","IP degree of protection":"IP20","Magnetic tripping limit":"3...5 x In","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"1","Product or component type":"Circuit breaker","Contact position indicator":"Yes","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","[Ue] rated operational voltage":"240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A conforming to EN 60898-1 - 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/370b71de24f66eeec9f2bfce11aabe60.pdf","sourceUrl":"https://www.se.com/ie/en/product/A9F56110/acti9-ikq-1p-10-a-b-miniature-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F56110/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9F56110?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of the A9F56110?","answer":"10,000 A Icn at 240 V AC per EN 60898-1, with a service breaking capacity (Ics) of 7,500 A at the same voltage."},{"question":"What is the A9F56110's depth?","answer":"78.5 mm."},{"question":"What range is the A9F56110 part of?","answer":"It's in the Acti9 range, Schneider's current-generation miniature circuit breaker platform for residential and commercial distribution."},{"question":"What compliance documentation does the A9F56110 carry?","answer":"It's certified to EN/IEC 60898-1. Pollution degree 2, overvoltage category III. Rated insulation voltage 440 V AC."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F56110","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F56110 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}