{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F58106","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F58106","canonicalUrl":"https://aoctrl.com/schneider/A9F58106","factsUrl":"https://aoctrl.com/api/mcp/products/A9F58106","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 IKQ, miniature circuit breaker, 1P, 6 A, D curve, 10 kA Icn at 240 V AC, EN/IEC 60898-1.","salesMarkdown":"The Schneider Electric A9F58106 is a 1-pole Acti9 IKQ miniature circuit breaker rated 6 A with a D tripping curve, meaning the magnetic release operates at 10 to 14 times the rated current — sized for loads with high inrush such as small motors, transformers, or lighting ballasts where a B or C curve would nuisance-trip on startup. Its 10 kA Icn breaking capacity at 240 V AC (EN 60898-1) and 7.5 kA Ics service breaking capacity at the same voltage give it enough fault-interrupting headroom for most residential and light commercial distribution boards fed from a typical utility transformer. The thermal-magnetic trip unit provides overload protection via the bimetal element and short-circuit protection via the solenoid — no earth-leakage function integrated, so any residual-current protection must come from a separate RCCB or RCBO downstream. Terminals accept 1 to 25 mm² rigid or 1 to 16 mm² flexible cable at the bottom connection; tighten to 2 N·m with a strip length of 14 mm. The toggle actuator provides manual on/off control, and a trip indicator shows the breaker has operated on fault. Padlockable for lockout/tagout during maintenance. Rated for 10,000 electrical and 20,000 mechanical cycles — suitable for frequent switching applications where the breaker also serves as a disconnect under load.","metaTitle":"Schneider Electric A9F58106 Acti9 IKQ MCB, D Curve 6 A, 10 k","metaDescription":"Schneider Electric A9F58106 Acti9 IKQ 1P MCB, D curve 6 A, 10 kA breaking capacity at 240 V AC, EN/IEC 60898-1. Current lifecycle stage, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"18 mm","Colour":"White","Height":"85 mm","Standards":"EN/IEC 60898-1","Curve code":"D","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC","Product name":"IKQ","Mounting mode":"Plug-on","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"Rail","Pollution degree":"2 conforming to EN/IEC 60898-1","Breaking capacity":"10000 A Icn at 240 V AC 50/60 Hz conforming to EN 60898-1","Network frequency":"50/60 Hz","Poles description":"1P","Tightening torque":"2 N.m bottom","[In] rated current":"6 A","Overvoltage category":"III","Trip unit technology":"Thermal-magnetic","Electrical durability":"10000 cycles","Mechanical durability":"20000 cycles","Wire stripping length":"14 mm for bottom connection","Connections - terminals":"Single terminal (bottom) 1...25 mm² rigid Single terminal (bottom) 1...16 mm² flexible","IP degree of protection":"IP20","Magnetic tripping limit":"10...14 x In","Earth-leakage protection":"Without","Provision for padlocking":"Padlockable","Number of protected poles":"1","Product or component type":"Circuit breaker","Contact position indicator":"Yes","[Ui] rated insulation voltage":"440 V AC 50/60 Hz conforming to EN/IEC 60898-1","[Ue] rated operational voltage":"240 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-25...60 °C","[Ics] rated service breaking capacity":"7500 A conforming to EN 60898-1 - 240 V AC 50/60 Hz","[Uimp] rated impulse withstand voltage":"4 kV conforming to EN/IEC 60898-1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dbb53de20cc4ca83daffd1ea94c4e178.pdf","sourceUrl":"https://www.se.com/ie/en/product/A9F58106/acti9-ikq-1p-6-a-d-miniature-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F58106/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F58106 and get a price?","answer":"The A9F58106 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the D curve on this MCB for?","answer":"The D curve (magnetic trip 10–14 x In) is intended for loads with high inrush current such as small motors, transformers, or discharge lighting where a B or C curve would trip on startup."},{"question":"What breaking capacity does A9F58106 have?","answer":"The A9F58106 has a 10 kA Icn breaking capacity at 240 V AC (EN 60898-1) and a 7.5 kA Ics service breaking capacity at the same voltage."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F58106","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F58106 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}