{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F64203","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F64203","canonicalUrl":"https://aoctrl.com/schneider/A9F64203","factsUrl":"https://aoctrl.com/api/mcp/products/A9F64203","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti 9 iC60 A9F64203 miniature circuit breaker, 2-pole, 3 A rated, C-curve, 10 kA breaking capacity (Icu) per IEC 60947-2, 6 kV impulse withstand, thermal-magnetic trip, toggle control, IP20, clip-on mounting.","salesMarkdown":"## Overview The A9F64203 is a Schneider Acti 9 iC60 miniature circuit breaker rated 3 A with a C-curve magnetic trip (8 x In +/- 20 %), switching 2 poles on a 220 V AC network at 50/60 Hz. It carries a 10 kA breaking capacity (Icu) per IEC 60947-2 and meets both EN/IEC 60947-2 and EN/IEC 60898-1, with a 6 kV impulse withstand voltage and suitability for isolation per both standards. Compared to the 1-pole A9F74602 (50 kA Icu, 2 A), the A9F64203 offers 2 poles at 3 A with a 10 kA breaking capacity — choose the A9F74602 when the BOM requires a single-pole device with higher fault current headroom.","metaTitle":"Schneider A9F64203 Acti 9 iC60 MCB, 2-pole, 3 A, C-curve","metaDescription":"Schneider A9F64203 Acti 9 iC60 miniature circuit breaker: 2-pole, 3 A, C-curve, 10 kA breaking capacity, 6 kV impulse withstand, dual-standard IEC 60947-2 / 60898-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Range":"Acti9","Width":"36 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60","Mounting mode":"Clip-on Removable comb busbar installed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"35 mm DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60a","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"3 A","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) , for 1 cable(s) , 1...25 mm², rigid, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible, copper Single terminal (top or bottom) , for 1 cable(s) , 1...16 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory","IP degree of protection":"IP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"10 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA 100 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$46.20","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/76a51369bd89fc3a6a1256abbdf41823.pdf","sourceUrl":"https://www.se.com/vn/en/product/A9F64203/ic60a-miniature-circuit-breaker-2p-3-a-c-curve/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F64203/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F64203","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F64203 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}