{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F64332","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F64332","canonicalUrl":"https://aoctrl.com/schneider/A9F64332","factsUrl":"https://aoctrl.com/api/mcp/products/A9F64332","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iC60 A9F64332 miniature circuit breaker, 3-pole, 32 A rated current, C-curve, 10 kA Icu at 240 V AC, thermal-magnetic trip unit, IP20, clip-on DIN rail mount.","salesMarkdown":"## Overview The A9F64332 is a Schneider Acti9 iC60 miniature circuit breaker rated 32 A with a C-curve magnetic trip (8 x In +/- 20 %), switching a 3-pole AC load at 240 V and breaking up to 10 kA Icu per EN/IEC 60947-2 and EN/IEC 60898-1. The thermal-magnetic trip unit and IP20 finger-safe terminals suit distribution panelboards; the clip-on mounting accepts a removable comb busbar. The 10 kA Icu covers standard utility fault levels; for installations with higher available fault current or DC loads, step up to the iC60H series. Compared to the A9F89332 (iC60H, 42 kA Icu, 133 V AC/DC), the A9F64332 is limited to 10 kA Icu and AC only. The A9F89332 also supports DC networks and includes top/bottom comb busbar compatibility. Pick the A9F89332 when the panel's SCCR exceeds 10 kA or the circuit requires DC interruption.","metaTitle":"Schneider A9F64332 Acti9 iC60 MCB, 3-pole, 32 A, C-curve, 10 kA","metaDescription":"Schneider A9F64332 Acti9 iC60 miniature circuit breaker: 3-pole, 32 A, C-curve, 10 kA Icu, 240 V AC, thermal-magnetic trip, IP20, clip-on mounting.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"78.5 mm","Range":"Acti9","Width":"54 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC","Product name":"Acti9 iC60","Mounting mode":"Clip-on Removable comb busbar installed","Tropicalisation":"2 conforming to IEC 60068-1","lifecycle_stage":"current","Connection pitch":"18 mm between phases","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"35 mm DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 4500 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iC60a","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 %","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"32 A","Overvoltage category":"II","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) , for 1 cable(s) , 1...35 mm², rigid, copper Single terminal (top or bottom) , for 3.0 cable(s) , 16 mm², rigid, copper, with accessory Single terminal (top or bottom) , for 1.0 cable(s) , 50 mm², rigid, aluminium, with accessory Single terminal (top or bottom) , for 1.0 cable(s) , 1...25 mm², flexible, copper Single terminal (top or bottom) , for 1.0 cable(s) , 1...25 mm², flexible with ferrule, copper Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory Single terminal (top or bottom) , for 3 cable(s) , 10 mm², flexible, copper, with accessory","IP degree of protection":"IP20 conforming to IEC 60529 IP40 in modular enclosure (Insulation class II) conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Separate block","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Ue] rated operational voltage":"220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"10 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA 100 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$56.93","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2f0f1d7d27594794d88147a48c2b9ca3.pdf","sourceUrl":"https://www.se.com/be/en/product/A9F64332/miniature-circuit-breaker-mcb-acti9-ic60a-3p-32a-c-curve-4500a-iec-en-608981-6ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F64332/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F64332","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F64332 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:21:01.794Z","lastPublished":"2026-09-02T08:21:01.794Z","indexable":true}}