{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68110","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68110","canonicalUrl":"https://aoctrl.com/schneider/A9F68110","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68110","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60N, miniature circuit breaker, 1P, 10 A, C-curve, 10 kA Icu at 230 V AC, 18 mm, DIN rail.","salesMarkdown":"The Schneider Electric A9F68110 is an Acti9 iT60N miniature circuit breaker — 1-pole, 10 A rated current, C-curve thermal-magnetic trip. It breaks 10 kA Icu at 220…240 V AC (EN/IEC 60947-2) and 6000 A Icn at 230 V AC (EN/IEC 60898-1). The 18 mm width snaps onto a DIN rail, leaving two 9 mm pitches occupied in the enclosure. The C-curve magnetic trip triggers at 8 x In ±20 % — that is 80 A instantaneous, ±16 A. That suits it for mixed resistive-inductive loads where inrush is moderate (lighting banks, small motor circuits, control transformers). Mounts on a DIN rail (EN/IEC 60715). Terminal accepts 1…25 mm² rigid or 1…16 mm² flexible copper — strip 14 mm, torque to 2 N·m. The removable comb busbar profile is compatible with the Acti9 range for daisy-chaining phases across multiple poles. IP20 B finger-safe terminals; no additional touch protection needed inside a closed panel. Ambient storage range -40…85 °C covers most site conditions; operating altitude 0…2000 m without derating.","metaTitle":"Schneider Electric A9F68110 Acti9 iT60 MCB, 10 A C-Curve, 1P","metaDescription":"Schneider Electric A9F68110 Acti9 iT60 miniature circuit breaker, 10 A rated, C-curve, 1-pole, 18 mm wide. Breaking capacity 10 kA at 230 V AC. DIN rail mount. Current lifecycle st","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["1-Pole MCB (DIN Rail)"],"specifications":{"Range":"Acti9","Width":"18 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"2","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Embedding depth":"44 mm","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"1P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"10 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"1","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...60 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 100...133 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - 12...60 V DC 10 kA 100 % conforming to EN/IEC 60947-2 - 60...72 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68110/miniature-circuit-breaker-mcb-acti9-it60n-1p-10a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68110/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F68110 and get pricing?","answer":"The A9F68110 is available to order through our distribution channel. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the breaking capacity of A9F68110 at 230 V AC?","answer":"At 220…240 V AC 50/60 Hz, the Icu per IEC 60947-2 is 10 kA; the Icn per IEC 60898-1 at 230 V AC is 6000 A."},{"question":"What standards does A9F68110 comply with?","answer":"It complies with EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial). It is certified for isolation under both standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68110","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68110 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}