{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68201","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68201","canonicalUrl":"https://aoctrl.com/schneider/A9F68201","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68201","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60N miniature circuit-breaker, A9F68201, 1 A rated current, C-curve, 2-pole, 50 kA breaking capacity at 415 V AC, thermal-magnetic trip, DIN-rail mount.","salesMarkdown":"The Schneider Electric A9F68201 is a 1 A, 2-pole miniature circuit-breaker from the Acti9 iT60N range, built for distribution boards where a C-curve trip characteristic is needed to handle moderate inrush from small motor or lighting loads. The C-curve means magnetic tripping occurs at 8 x In (±20 %) — so at 1 A rated current, the instantaneous trip threshold sits around 8 A, which keeps it from nuisance-tripping on capacitor or transformer inrush while still clearing a hard fault fast. Breaking capacity is the headline here: 50 kA Icu at 415 V AC (per EN/IEC 60947-2) and 10 kA Icn at 400 V AC (per EN/IEC 60898-1). The 10 kA Icn rating under 60898-1 is the standard domestic/commercial service capacity; the 50 kA Icu under 60947-2 is the industrial ultimate capacity, giving you SCCR headroom for coordination studies. ## Integration and compliance details DIN-rail mount, 36 mm wide, with a removable comb busbar installed for easy phase linking. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible wire; strip length 14 mm, torque to 2 N·m. IP20 finger-safe (B type per IEC 60529). Pollution degree 3, overvoltage category IV — suitable for main distribution panels, not just sub-distribution. Ambient operating range -35…70 °C, storage -40…85 °C, with tropicalisation level 2 (conforming to EN/IEC 60068-2-78 for 95 % RH). Isolation capability is confirmed per both 60898-1 and 60947-2, with a visible contact position indicator and a trip indicator for quick fault identification.","metaTitle":"Schneider Electric A9F68201 Acti9 iT60 MCB, 1 A C-Curve 2P 5","metaDescription":"Schneider Electric A9F68201 Acti9 iT60 miniature circuit-breaker, 1 A rated, C-curve, 2-pole, 50 kA breaking capacity at 415 V AC. EN/IEC 60947-2 & 60898-1. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Range":"Acti9","Width":"36 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"1 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68201/miniature-circuit-breaker-mcb-acti9-it60n-2p-1a-c-curve-6000a-iec-en-608981-50ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68201/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F68201?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of A9F68201 at 415 V?","answer":"50 kA Icu at 380…415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V per EN/IEC 60898-1."},{"question":"What standards does A9F68201 comply with?","answer":"It complies with EN/IEC 60947-2 and EN/IEC 60898-1, with isolation capability confirmed under both standards."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68201","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68201 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}