{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68206","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68206","canonicalUrl":"https://aoctrl.com/schneider/A9F68206","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68206","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, miniature circuit breaker, 6 A, C-curve, 2P, 36 mm, breaking capacity 36 kA at 133 V AC.","salesMarkdown":"The Schneider Electric A9F68206 is a 6 A, C-curve, 2-pole miniature circuit breaker from the Acti9 iT60 series, designed for distribution in final-subdivision panels. Its thermal-magnetic trip unit handles overloads and short-circuits, with a magnetic tripping threshold of 8 × In ±20 % — meaning it holds through moderate inrush but clears fast on a hard fault. The 36 mm width takes up two standard 18 mm pitches on a DIN rail, so it fits a 4-module space. The breaking capacity varies with voltage: 36 kA Icu at 12…133 V AC, 20 kA at 220…240 V, 10 kA at 380…415 V, and 6 kA at 440 V. At 400 V it also carries a 10 kA Icn under EN/IEC 60898-1. For a 6 A MCB in a 230/400 V panel, the 20 kA at 240 V and 10 kA at 400 V are the figures that govern selectivity with an upstream device — the limitation class 3 means it lets through less energy, easing coordination. The removable comb busbar allows daisy-chaining phases across multiple breakers without extra wiring. Terminals accept 1…25 mm² rigid or 1…16 mm² flexible; strip length 14 mm, torque to 2 N·m.","metaTitle":"Schneider Electric A9F68206 Acti9 iT60 MCB, 6 A C-curve 2P 3","metaDescription":"Schneider Electric A9F68206 Acti9 iT60 miniature circuit breaker, 6 A rated, C-curve, 2-pole, 36 mm wide, 36 kA breaking capacity at 133 V AC. Available to order; confirm current p","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Range":"Acti9","Width":"36 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"6 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68206/miniature-circuit-breaker-mcb-acti9-it60n-2p-6a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68206/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F68206 at 400 V?","answer":"At 380…415 V AC the Icu is 10 kA per EN/IEC 60947-2, and the Icn at 400 V per EN/IEC 60898-1 is also 10 kA."},{"question":"Where can I buy A9F68206?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the width of A9F68206?","answer":"It is 36 mm wide, occupying two standard 18 mm DIN-rail pitches."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68206","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68206 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}