{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68216","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68216","canonicalUrl":"https://aoctrl.com/schneider/A9F68216","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68216","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, A9F68216, miniature circuit breaker, 2P, 16 A rated current, C curve, 10 kA breaking capacity at 400 V AC, DIN rail mount.","salesMarkdown":"The A9F68216 is a 2-pole Acti9 iT60 miniature circuit breaker rated 16 A with a C curve — magnetic trip at 8 x In ±20 %, so it holds moderate inrush from motor starters or small transformers without nuisance tripping, while still clearing a hard short fast enough for downstream coordination. Breaking capacity is the headline: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, and 10 kA Icu at 380–415 V — plus 6 kA Icu at 440 V — all per EN/IEC 60947-2. For distribution duty under EN/IEC 60898-1 it carries 10 kA Icn at 400 V. That dual rating means it can serve either industrial feeder panels (60947-2) or commercial final circuits (60898-1) without swapping the part. Pollution degree 3 means it holds up in dirty or humid environments — the tropicalisation rating (2 conforming to EN/IEC 60068-2-78) backs that for 95 % RH. The removable comb busbar is already installed — wire up single terminals top or bottom, 1–25 mm² rigid or 1–16 mm² flexible, strip 14 mm, torque to 2 N·m. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household / commercial). Suitability for isolation is confirmed under both standards. IP20 B finger protection on the front face.","metaTitle":"Schneider Electric A9F68216 Acti9 iT60 MCB, 16 A, C Curve, 1","metaDescription":"Schneider Electric A9F68216 Acti9 iT60 miniature circuit breaker, 16 A rated current, C curve, 10 kA breaking capacity at 400 V AC. Dual-rated to EN/IEC 60947-2 and 60898-1. Source","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Range":"Acti9","Width":"36 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68216/miniature-circuit-breaker-mcb-acti9-it60n-2p-16a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68216/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F68216 at 400 V?","answer":"10 kA Icu at 380–415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V per EN/IEC 60898-1."},{"question":"Where can I buy A9F68216 and get current pricing?","answer":"Sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time."},{"question":"What compliance standards does A9F68216 meet?","answer":"Certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation under both standards. Tropicalisation per EN/IEC 60068-2-78."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68216","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68216 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}