{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68220","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68220","canonicalUrl":"https://aoctrl.com/schneider/A9F68220","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68220","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, A9F68220, miniature circuit-breaker, 2P, C-curve, 20 A, 36 kA breaking capacity at 133 V AC, DIN rail mount.","salesMarkdown":"The Schneider Electric A9F68220 is a 2-pole miniature circuit-breaker from the Acti9 iT60 range, rated 20 A with a C-curve trip characteristic (magnetic tripping at 8 x In ±20 %). At 400 V AC the breaking capacity is 10 kA Icu (IEC 60947-2) and 6 kA Icn (IEC 60898-1), which covers most commercial distribution boards. The C-curve means it holds through motor inrush and moderate transformer starts but trips fast on a hard short. IP20 B rated for dry indoor panels only; not for washdown or outdoor use. Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household/domestic). That means it can be used in commercial distribution panels (60947-2) and also in residential consumer units (60898-1) — one part for both worlds. Isolation capability is confirmed per both standards.","metaTitle":"A9F68220 Acti9 iT60 MCB, 2P C-curve 20 A, 36 kA","metaDescription":"Schneider Acti9 iT60 miniature circuit-breaker A9F68220, 2-pole C-curve 20 A, 36 kA breaking capacity at 133 V AC. Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Range":"Acti9","Width":"36 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"20 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68220/miniature-circuit-breaker-mcb-acti9-it60n-2p-20a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68220/alternatives.json"},"ai":{"faq":[{"question":"Who supplies A9F68220 and how is it quoted for volume purchases?","answer":"The part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no fixed stock or price is published here."},{"question":"What is A9F68220's breaking capacity at 400 V?","answer":"At 400 V AC 50/60 Hz the breaking capacity is 10 kA Icu per IEC 60947-2 and 6 kA Icn per IEC 60898-1. At 133 V AC it reaches 36 kA Icu."},{"question":"What is the width of A9F68220?","answer":"36 mm, which corresponds to 4 x 9 mm pitches on a DIN rail. Standard for a 2-pole MCB."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68220","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68220 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}