{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68263","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68263","canonicalUrl":"https://aoctrl.com/schneider/A9F68263","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68263","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60N, A9F68263, miniature circuit breaker, 63 A, C curve, 2 poles, 36 mm wide, thermal-magnetic trip, breaking capacity 36 kA at 133 V AC.","salesMarkdown":"The Schneider Electric A9F68263 is an Acti9 iT60N miniature circuit breaker rated at 63 A with a C-curve trip characteristic, 2 poles, and a 36 mm DIN-rail footprint. Breaking capacity reaches 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V AC, and 10 kA at 380–415 V AC per EN/IEC 60947-2; under EN/IEC 60898-1 it delivers 10 kA Icn at 400 V AC. That dual rating means the same unit satisfies both industrial (60947-2) and residential/commercial (60898-1) installations, simplifying BOM consolidation. ## Integration and wiring constraints Mounts on DIN rail with a removable comb busbar installed. Terminals accept 1–35 mm² rigid or 1–25 mm² flexible wire; strip length is 14 mm. IP20 B finger-safe terminals per IEC 60529. Tropicalisation class 2 per EN/IEC 60068-2-78 handles 95% relative humidity. Dual certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial). Suitability for isolation confirmed under both standards. Local trip indicator and contact position indicator are standard.","metaTitle":"Schneider Electric A9F68263 Acti9 iT60 MCB, 63 A, C Curve, 2","metaDescription":"Schneider Electric A9F68263 Acti9 iT60 miniature circuit breaker, 63 A rated current, C curve, 2 poles, 36 mm wide. Breaking capacity 36 kA at 133 V AC, 10 kA at 415 V AC. Current","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["2-Pole MCB (DIN Rail)"],"specifications":{"Range":"Acti9","Width":"36 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"4","Control type":"Toggle","Network type":"DC AC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"2P","Relative humidity":"95 %","Tightening torque":"3.5 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"63 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...35 mm² rigid Single terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"2","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68263/miniature-circuit-breaker-mcb-acti9-it60n-2p-63a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68263/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy A9F68263 and what is the lead time?","answer":"The A9F68263 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of A9F68263 at 400 V AC?","answer":"The A9F68263 delivers 10 kA Icu at 380–415 V AC per EN/IEC 60947-2 and 10 kA Icn at 400 V AC per EN/IEC 60898-1."},{"question":"What wire sizes does A9F68263 accept?","answer":"Terminals accept 1–35 mm² rigid or 1–25 mm² flexible wire with a strip length of 14 mm and tightening torque of 3.5 N.m."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68263","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68263 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}