{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68304","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68304","canonicalUrl":"https://aoctrl.com/schneider/A9F68304","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68304","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, A9F68304, miniature circuit breaker, 3P, 4 A, C curve, 50 kA Icu at 415 V AC, DIN rail.","salesMarkdown":"It breaks up to 50 kA Icu at 415 V AC (EN/IEC 60947-2) and carries a 10 kA Icn at 400 V (EN/IEC 60898-1), so it handles high fault currents typical in distribution panels while still meeting residential-standard coordination. Rated Icu of 50 kA at 220–240 V and 380–415 V AC per EN/IEC 60947-2. C curve trips magnetically at 8 x In ±20 %. Suitability for isolation per both standards. Snaps onto DIN rail, occupies 54 mm (6 x 9 mm pitches). Terminals accept 1–25 mm² rigid or 1–16 mm² flexible; tightening torque 2 N·m. Removable comb busbar. IP20 finger-safe terminals, pollution degree 3, overvoltage category IV — rated for the main distribution board, not just sub-panels. Ambient operation from -35 to 70 °C covers most indoor enclosures even near hot busbars. Lifecycle status is current. Standard catalogue item in the Acti9 range.","metaTitle":"A9F68304 Acti9 iT60 MCB, 4 A, C Curve, 50 kA, 3P","metaDescription":"Schneider Electric A9F68304 Acti9 iT60 miniature circuit breaker, 4 A rated current, C curve, 50 kA breaking capacity at 415 V AC, 3 poles, DIN rail mount. Current lifecycle, sourc","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"Acti9","Width":"54 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"4 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68304/miniature-circuit-breaker-mcb-acti9-it60n-3p-4a-c-curve-6000a-iec-en-608981-50ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68304/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of A9F68304?","answer":"50 kA Icu at 380–415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V per EN/IEC 60898-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68304","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68304 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}