{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"A9F68316","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"A9F68316","canonicalUrl":"https://aoctrl.com/schneider/A9F68316","factsUrl":"https://aoctrl.com/api/mcp/products/A9F68316","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Acti9 iT60, miniature circuit breaker, 16 A, C curve, 3P, 54 mm, DIN rail, thermal-magnetic, dual standard EN/IEC 60947-2 and 60898-1.","salesMarkdown":"The A9F68316 is a 16 A, 3-pole miniature circuit breaker from Schneider Electric's Acti9 iT60 range, with a C curve (magnetic trip at 8 × In ±20 %). Breaking capacity is dual-rated: 10 kA Icn at 400 V AC per EN/IEC 60898-1 (the household-standard rating), and 10 kA Icu at 380–415 V AC per EN/IEC 60947-2 (the industrial-standard rating). At 54 mm wide (6 × 9 mm pitches), it occupies three modular spaces — the standard width for a 3-pole MCB. Removable comb busbar installed means it's ready for daisy-chaining line-side feeds across a row of breakers without extra wiring. Tropicalisation class 2 per EN/IEC 60068-2-78 means it withstands 95 % relative humidity — relevant for coastal or unconditioned plant rooms. No official successor or direct cross-reference exists because it's the active model. If you're maintaining an older panel that used the previous-generation Multi9 or C60 range, the Acti9 iT60 is the direct functional replacement — same footprint, same curve, same breaking capacity class.","metaTitle":"Schneider Electric A9F68316 Acti9 iT60 MCB, 16 A, C Curve, 3","metaDescription":"Schneider Electric A9F68316 Acti9 iT60 miniature circuit breaker, 16 A rated current, C curve, 3-pole, 54 mm wide. Dual-rated to EN/IEC 60947-2 and 60898-1. Current lifecycle stage","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Miniature Circuit Breakers (MCB)"],"specifications":{"Range":"Acti9","Width":"54 mm","Colour":"White","Standards":"EN/IEC 60947-2 EN/IEC 60898-1","Curve code":"C","9 Mm Pitches":"6","Control type":"Toggle","Network type":"AC/DC","Product name":"Acti9 iT60","Mounting mode":"Removable comb busbar installed","Tropicalisation":"2 conforming to EN/IEC 60068-2-78","lifecycle_stage":"current","Limitation class":"3 conforming to EN/IEC 60898-1","Local signalling":"Trip indicator","Mounting support":"DIN rail","Pollution degree":"3 conforming to EN/IEC 60947-2","Breaking capacity":"36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1","Device short name":"iT60N","Network frequency":"50/60 Hz","Poles description":"3P","Relative humidity":"95 %","Tightening torque":"2 N.m top or bottom","Device application":"Distribution","Operating altitude":"0...2000 m","[In] rated current":"16 A","Overvoltage category":"IV","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A conforming to EN/IEC 60947-2","Wire stripping length":"14 mm for top or bottom connection","Connections - terminals":"Single terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible","IP degree of protection":"IP20 B conforming to IEC 60529","Magnetic tripping limit":"8 x In +/- 20 %","Earth-leakage protection":"Without","Number of protected poles":"3","Product or component type":"Miniature circuit-breaker","Suitability for isolation":"Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2","Contact position indicator":"Yes","[Ui] rated insulation voltage":"500 V AC 50/60 Hz conforming to EN/IEC 60947-2","Ambient air temperature for storage":"-40...85 °C","Ambient air temperature for operation":"-35...70 °C","[Ics] rated service breaking capacity":"27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC","[Uimp] rated impulse withstand voltage":"6 kV conforming to EN/IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://www.se.com/be/en/product/A9F68316/miniature-circuit-breaker-mcb-acti9-it60n-3p-16a-c-curve-6000a-iec-en-608981-10ka-iec-en-609472/","alternativesUrl":"https://aoctrl.com/api/mcp/products/A9F68316/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the A9F68316 and get a price?","answer":"The A9F68316 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your target quantity and delivery window."},{"question":"What are the key ratings of the A9F68316?","answer":"Rated current 16 A, C curve, 3-pole, breaking capacity 10 kA at 400 V AC (Icn per EN/IEC 60898-1 and Icu per EN/IEC 60947-2), thermal-magnetic trip, suitable for isolation, 54 mm wide, DIN rail mount."},{"question":"What standards does the A9F68316 comply with?","answer":"It is dual-rated to EN/IEC 60947-2 (industrial standard) and EN/IEC 60898-1 (household standard). It also carries tropicalisation class 2 per EN/IEC 60068-2-78 and pollution degree 3 per EN/IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/A9F68316","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/A9F68316 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}